Specifications
25
Table 2 — CVC Display Data (cont)
EXAMPLE 6 — POWER DISPLAY SCREEN
To access this displa
y
from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to hi
g
hli
g
ht .
4. Press
.
NOTES:
1. All variables with CAPITAL LETTER point names are available for CCN read operation.
2. Those shown with (**) shall support write operations for CVC only.
EXAMPLE 7 — ISM_STAT DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press
.
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
DESCRIPTION STATUS UNITS POINT
Average Line Current
0-999 % %_AMPS
Actual Line Current
0-99999 AMPS AMP_A
Average Line Voltage
0-999 % VOLT_P
Actual Line Voltage
0-99999 VOLTS VOLT_A
Power Factor
0.0-1.0 PF
Motor Kilowatts
0-99999 kW KW_A
**Motor Kilowatt-Hours
0-99999 kWH KWH
Demand Kilowatts
0-99999 kWH DEM_KWH
Line Current Phase 1
0-99999 AMPS AMPS_1
Line Current Phase 2
0-99999 AMPS AMPS_2
Line Current Phase 3
0-99999 AMPS AMPS_3
Line Voltage Phase 1
0-99999 VOLTS VOLTS_1
Line Voltage Phase 2
0-99999 VOLTS VOLTS_2
Line Voltage Phase 3
0-99999 VOLTS VOLTS_3
Ground Fault Phase 1
0-999 AMPS GF_1
Ground Fault Phase 2
0-999 AMPS GF_2
Ground Fault Phase 3
0-999 AMPS GF_3
Frequency
0-99 Hz FREQ
I2T Sum Heat-Phase 1
0-200 % HEAT1SUM
I2T Sum Heat-Phase 2
0-200 % HEAT2SUM
I2T Sum Heat-Phase 3
0-200 % HEAT3SUM
DESCRIPTION STATUS UNITS POINT
ISM Fault Status
0-223 ISMFLT
Single Cycle Dropout
0-1 NORMAL/ALARM CYCLE_1
Phase Loss
0-1 NORMAL/ALARM PH_LOSS
Overvoltage
0-1 NORMAL/ALARM OV_VOLT
Undervoltage
0-1 NORMAL/ALARM UN_VOLT
Current Imbalance
0-1 NORMAL/ALARM AMP_UNB
Voltage Imbalance
0-1 NORMAL/ALARM VOLT_UNB
Overload Trip
0-1 NORMAL/ALARM OVERLOAD
Locked Rotor Trip
0-1 NORMAL/ALARM LRATRIP
Starter LRA Trip
0-1 NORMAL/ALARM SLRATRIP
Ground Fault
0-1 NORMAL/ALARM GRND_FLT
Phase Reversal
0-1 NORMAL/ALARM PH_REV
Frequency Out of Range
0-1 NORMAL/ALARM FREQFLT
ISM Power on Reset
0-1 NORMAL/ALARM ISM_POR
Phase 1 Fault
0-1 NORMAL/ALARM PHASE_1
Phase 2 Fault
0-1 NORMAL/ALARM PHASE_2
Phase 3 Fault
0-1 NORMAL/ALARM PHASE_3
1CR Start Complete
0-1 FALSE/TRUE START_OK
1M Start/Run Fault
0-1 NORMAL/ALARM 1M_FLT
2M Start/Run Fault
0-1 NORMAL/ALARM 2M_FLT
Pressure Trip Contact
0-1 NORMAL/ALARM PRS_RIP
Starter Fault
0-1 NORMAL/ALARM STRT_FLT
Motor Amps Not Sensed
0-1 NORMAL/ALARM NO_AMPS
Starter Acceleration Fault
0-1 NORMAL/ALARM ACCELFLT
High Motor Amps
0-1 NORMAL/ALARM HIGHAMPS
1CR Stop Complete
0-1 FALSE/TRUE STOP_OK
1M/2M Stop Fault
0-1 NORMAL/ALARM 1M2MSTOP
Motor Amps When Stopped
0-1 NORMAL/ALARM AMPSTOP
Hardware Failure
0-1 NORMAL/ALARM HARDWARE
MENU
STATUS
POWER
SELECT
MENU
STATUS
ISM_STAT
SELECT