19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Comp Motor Temp Override
150 to 200 DEG F 200
Cond Press Override
90 to 165 PSI 125
Comp Discharge Alert
125 to 200 DEG F 200
Comp Thrust Brg Alert
165 to 185 DEG F 175
Chilled Medium
0/1 WATER/BRINE WATER
Chilled Water Deadband
.5 to 2.0 ˆF1.0
Evap Refrig Trippoint
0.0 to 40.0 DEG F 33
Refrig Override Delta T
2.0 to 5.0 ˆF3
Condenser Freeze Point
–20 to 35 DEG F 34
Evap Flow Delta P Cutout
0.5 to 50.0 PSI 5.0
Cond Flow Delta P Cutout
0.5 to 50.0 PSI 5.0
Water Flow Verify Time
0.5 to 5 MIN 5
Oil Press Verify Time
15 to 300 SEC 40
Recycle Control
Restart Delta T
2.0 to 10.0 DEG F 5
Shutdown Delta T
0.5 to 4.0 DEG F 1
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
0 to 4 0
Spare Temp #1 Limit
–40 to 245 DEG F 245
Spare Temp #2 Enable
0 to 4 0
Spare Temp #2 Limit
–40 to 245 DEG F 245