Specifications

6
Notes:
• 19XR units have a single power connection point.
• The control box includes the following standard features:
- Starter and compressor motor protection devices, or
- protection and control elements only
• Field connections:
All connections to the system and the electrical installations must be in full accordance
with all applicable codes.
• The Carrier 19XR units are designed and built to ensure conformance with local codes.
The recommendations of European standard EN 60204-1 (corresponds to IEC 60201-
1) (machine safety - electrical machine components - part 1: general regulations) are
specifically taken into account, when designing the electrical equipment.
Notes:
• Generally the recommendations of IEC 60364 are accepted as compliance with the
requirements of the installation directives. Conformance with EN 60204-1 is the best
means of ensuring compliance with the Machines Directive and § 1.5.1.
• Annex B of EN 60204-1 describes the electrical characteristics used for the operation of
the machines.
1. The operating environment for the 19XR units is specified below:
Environment* - Environment as classified in IEC 60364 § 3:
- ambient temperature range: +5°C to +40°C, class AA4*
- humidity range (non-condensing)*:
50% relative humidity at 40°C
90% relative humidity at 20°C
- altitude: ) 2000 m
- indoor installation
- presence of water: class AD2* (possibility of water droplets)
- presence of hard solids, class AE2* (no significant dust present)
- presence of corrosive and polluting substances, class AF1 (negligible)
- vibration and shock, class AG2, AH2
Competence of personnel, class BA4* (trained personnel - IEC 60364)
2. Power supply frequency variation: ± 2 Hz.
3. The neutral (N) conductor must not be connected directly to the unit (if necessary use a
transformer).
4. Overcurrent protection of the power supply conductors is not provided with the unit.
5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) disconnect devices
of a type suitable for power interruption in accordance with EN 60947-3 (corresponds to
IEC 60947-3).
6. The units are designed for connection to TN networks (IEC 60364). For IT networks the
earth connection must not be at the network earth. Provide a local earth, consult
competent local organisations to complete the electrical installation.
Note:
If particular aspects of an actual installation do not conform to the conditions described
above, or if there are other conditions which should be considered, always contact your
local Carrier representative.
* The protection level required to conform to this class is IP21B (according to reference
document IEC 60529). All 19XR units are protected to IP23C and fulfil this protection
condition.
General electrical data
Standard voltages:
50 Hz
Volt For use on supply voltages
230 220 to 240 V systems
346 320 to 360 V systems
400 380 to 415 V systems
3000 2900 to 3100 V systems
3300 3200 to 3400 V systems
6300 6000 to 6600 V systems
Notes:
Motor nameplates can be stamped for any voltage within the listed supply/
voltage range. Chillers shall not be selected at voltages above or below the
listed supply voltage range.
Auxiliary ratings (3 Phase, 50 Hz)
Item Average Design Min./max. Inrush Sealed
kW centre motor kVA kVA
voltage voltage
V-Ph-Hz V
Oil pump 1.50 230-3-50 220/240 11.15 1.93
1.50 393-3-50 346/440 8.30 1.76
IkW = Compressor motor power input (kW)
RLA = (rated load amperes) = Sealed kVA x 1000/33 x volts
LRA = (locked rotor amperes) = Inrush kVA x 1000/33 x volts
Auxiliary ratings (115/230 V, 1 phase, 50 Hz)
Item Voltage Sealed kVA Average W
Controls 24 V a.c. 0.16 160
Oil sump heater 115/1/50 1800
Notes:
1. Oil sump heater only operates when the compressor is off.
2. Power to oil heater/controls must be on circuits that can provide continuous service when
the compressor is disconnected.