Specifications

D
1
2
3
5
4
A
B
C
E
12
Dimensions
Heat A (length, with nozzle-in-head B (width) C (height) A (length, marine waterbox D E
exchanger waterbox) - not shown)
size 2-pass* 1 or 3 pass** 2-pass* 1 or 3 pass**
mm mm mm mm mm mm mm mm
30 to 32 4172 4350 1670 2073 4496 4997 3747 250
35 to 37 4693 4870 1670 2073 5017 5518 4343 250
40 to 42 4242 4426 1880 2153 4591 5099 3757 250
45 to 47 4763 4947 1880 2153 5099 5620 4343 250
50 to 52 4248 4439 1994 2207 4591 5099 3747 250
55 to 57 4769 4959 1994 2207 5099 5620 4343 250
60 to 62 4261 4451 2096 2257 4591 5111 3747 250
65 to 67 4782 4972 2096 2257 5112 5632 4343 250
70 to 72 4978 5194 2426 2985 5385 6058 4267 460
75 to 77 5588 5804 2426 2985 5994 6668 4877 460
80 to 82 4997 5220 2711 3029 5398 6121 4267 460
85 to 87 5607 5829 2711 3029 6007 6731 4877 460
* Assumes both cooler and condenser nozzles on same end of chiller.
** 1 or 3 pass length applies if either (or both) cooler or condenser is a 1 or 3 pass design.
Frame size Nozzle inlet/outlet size (in.) (nominal pipe size)
Cooler Condenser
1-Pass 2-Pass 3-Pass 1-Pass 2-Pass 3-Pass
3 10861086
4 10861086
5 108 6 10108
6 10 10 8 10 10 8
7 14 12 10 14 12 12
8 14 14 12 14 14 12
Notes:
1. Service clearance must comply with local regulations.
2. Certified drawings available upon request.
1. Motor service space (1219 mm)
2. Recommended clearance above the machine
(915 mm)
3. 610 mm
4. 362 mm
5. Tube removal space
E. Float valve removal space - variable,
depending on the unit height - see rear view on
the previous page, item 28