Operating instructions
61
A temperature sensor in the suction line is used by the
PIC III control to check that the flow rate in the heat
exchanger is not zero.
If flow detection by measuring the presure differential in
the water circuit is active, the two verifications are carried
out in parallel and cumulated.
Please refer to the 19XR PIC III controls manual.
50 kA rms
According to the variable-frequency drive
parameter set at the factory
. < 32 A
50/60 (± 2) Hz
*** ±10 %
> 0.97
Cosine phi > 0.99
Harmonic distortion index (THDI) < 5%
19xr-506---912: C3****
19xr-506---922: C3****
19xr-506---802: C3**** conducted emissions
C4* radiated emissions*
19xr-506---812: C3**** conducted emissions
C4* radiated emissions*
< 1000 m
Default factory control
Other possible control
4 kHz
2 kHz
65 to 100%
6000 W
9000 W
12000 W
18000 W
* Emission level according to level C3+5 dB(µV/m)
** Continuous bus load
*** Around the nominal value
**** According to standard 61800-3; installation in an industrial environment
19XRV machines are supplied with the electrical equipment
integrated, wired, pre-configured and tested at the factory.
The installation of the electrical equipment includes the
connection of customer auxiliary and communication power
supply cables, as well as configuration parameter adjust-
ment specific to the installation site.
During storage the machine must be protected against
humidity and dust. Specifically, the machine must not be
placed in an outside location, exposed to the weather.
10.3.1 - Unit rigging
ATTENTION: The control box must not be used as a
machine rigging point.
The 19XRV machine rigging points are the same as those
for the standard machine without variable-frequency drive.
Refer to the dimensional drawing supplied with the machine.
10.3.2 - Weights and dimensions
The data in this section is for information only. The contrac-
tual data is given on the dimensional drawing supplied with
the machine. The weight of 19XRV machines is the same as
that of standard machines plus weight of the control boxes.
19xr-506---912
19xr-506---922
19xr-506---802
19xr-506---812
750
750
1300
1300
19XRV machine dimensions are the same as for standard
machines; the height (only) is increased for machines
equipped with VFD control boxes 19XR-506---912 and
19XR-506---922.
2414
2501
2680
2721
N/A
N/A
These congurations (machine size and VFD size combination) are not possible.
19XRV machine dimensions are the same as for standard
machines; height and width are increased for machines
equipped with VFD control boxes 19XR-506---802 and
19XR-506---81.
N/A N/A
N/A N/A
2908 2036
2959 2127
3110 2920
3161 3165
** For these machines, the VFD is supplied, but not installed on the machine. The
dimensions given apply to the machine with the VFD installed.
These congurations (machine size and VFD size combination) are not possible.