Operating instructions

23
1. Anti-vibration platform
2. Soleplate
3. Adjusting pads
4. Adjusting screws
Accessory (Carrier supplied, eld-installed) soleplate package includes 4
anti-vibration platforms/soleplates, 16 adjusting screws and levelling pads.
Thickness of grout will vary, depending on the amount necessary to level chiller.
Use only pre-mixed non-shrinking grout. Celcote HT-648 or Master Builders 636,
38 to 57 mm thick.


3.4.3 - Install spring isolation
Spring isolation may be purchased as an accessory from
Carrier for field installation. It may also be field supplied
and installed.
Spring isolators may be placed directly under machine
support plates or located under machine soleplates. See
Fig. 15 - “19XR Spring isolation”.
Machine foot (side view)
System base (concrete)
1. Accessory spring isolator
2. Soleplate (accessory) attaches securely to isolator
3. Level foundation
4. Resilient shear ex pad, bonded to top and bottom of spring mount
5. Support plate
Obtain specific details on spring mounting and machine
weight distribution from job data. Also, check job data for
methods to support and isolate pipes that are attached to
spring isolated machines.