Specifications
Table 4 — 19XR Additional Data for Marine Waterboxes*
HEAT EXCHANGER
FRAME, PASS
ENGLISH SI
Psig
Rigging Weight
(lb)
Water Volume
(gal)
kPa
Rigging Weight
(kg)
Water Volume
(L)
Frame 3, 1 and 3 Pass 150 730 84 1034 331 317
Frame 3, 2 Pass 150 365 42 1034 166 159
Frame 4, 1 and 3 Pass 150 1060 123 1034 481 465
Frame 4, 2 Pass 150 530 61 1034 240 231
Frame 5, 1 and 3 Pass 150 1240 139 1034 562 526
Frame 5, 2 Pass 150 620 69 1034 281 263
Frame 6, 1 and 3 Pass 150 1500 162 1034 680 612
Frame 6, 2 Pass 150 750 81 1034 340 306
Frame 3, 1 and 3 Pass 300 860 84 2068 390 317
Frame 3, 2 Pass 300 430 42 2068 195 159
Frame 4, 1 and 3 Pass 300 1210 123 2068 549 465
Frame 4, 2 Pass 300 600 61 2068 272 231
Frame 5, 1 and 3 Pass 300 1380 139 2068 626 526
Frame 5, 2 Pass 300 690 69 2068 313 263
Frame 6, 1 and 3 Pass 300 1650 162 2068 748 612
Frame 6, 2 Pass 300 825 81 2068 374 306
*Add to heat exchanger data for total weights or volumes.
NOTE: Weight shown is total for cooler and condenser. Cooler and condenser of the same frame size are of equal weight.
Table 5 — 19XR Waterbox Cover Weights
ENGLISH (lb)
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 3 FRAME 4 FRAME 5 FRAME 6
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/CONDENSER
NIH, 1 Pass Cover, 150 psig 320 350 485 521 616 652 802 838
NIH, 2 Pass Cover, 150 psig 320 350 487 540 590 663 770 843
NIH, 3 Pass Cover, 150 psig 300 340 504 520 629 655 817 843
NIH/MWB End Cover or MWB 1*,
2, or 3* Pass Cover, 150 psig
300 300 379 379 428 428 583 583
MWB End Cover or MWB 1*,
2 or 3* Pass Cover, 300 psig
400 400 569 569 713 713 833 833
SI (kg)
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 3 FRAME 4 FRAME 5 FRAME 6
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/CONDENSER
NIH, 1 Pass Cover, 150 psig 145 159 220 236 279 296 364 380
NIH, 2 Pass Cover, 150 psig 145 159 221 245 268 301 349 382
NIH, 3 Pass Cover, 150 psig 140 154 229 236 285 297 371 381
NIH/MWB End Cover or MWB 1*, 2,
or 3* Pass Cover, 150 psig
136 136 172 172 194 194 264 264
MWB End Cover or MWB 1*, 2
or 3* Pass Cover, 300 psig
181 181 258 258 323 323 378 378
LEGEND
NIH — Nozzle-in-Head
MWB — Marine Waterbox
*Cooler only.
NOTE: Weight for NIH 2-pass cover, 150 psig, are included in heat exchanger
weights shown on page 7.
RIG MACHINE COMPONENTS — Refer to instructions
below, Fig. 5-8, and Carrier Certified Prints for machine com-
ponent disassembly.
IMPORTANT: Only a qualified service technician should
perform this operation.
Do not attempt to disconnect flanges while the machine
is under pressure. Failure to relieve pressure can result
in personal injury or damage to the unit.
Before rigging the compressor, disconnect all wires en-
tering the power panel.
NOTE: If the cooler and condenser vessels must be sepa-
rated, the heat exchangers should be kept level by placing a
support plate under the tube sheets. The support plate will
also help to keep the vessels level and aligned when the ves-
sels are bolted back together.
NOTE: Wiring must also be disconnected. Label each wire
before removal (see Carrier Certified Prints). In order to dis-
connect the starter from the machine, remove wiring for the
oil pump, oil heater, control wiring at the power panel, and
the main motor leads at the starter lugs.
Remove all transducer and sensor wires at the sensor. Clip
all wire ties necessary to pull heat exchangers apart.
To separate Cooler and Condenser:
1. Place a support plate under each tube sheet to keep each
vessel level (Fig. 5, Item 6).
2. Cut the refrigerant motor cooling line at the location shown
(Fig. 5, Item 7).
8