Specifications

options. The LID has a STOP button, an alarm light, 4 but-
tons for logic inputs, and a display. The function of the
4 buttons or ‘softkeys’ are menu driven and are shown on
the display directly above the key.
6-PACK RELAY BOARD This device is a cluster of
6 pilot relays located in the control center. It is energized by
the PSIO for the oil pump, oil heater, alarm, and optional hot
gas bypass relay.
8-INPUT MODULES One optional module is factory in-
stalled in the control center when ordered. There can be up
to 2 of these modules per chiller with 8 spare inputs each.
They are used whenever chilled water reset, demand reset,
or reading a spare sensor is required. The sensors or 4 to
20 mA signals are field-installed.
The spare temperature sensors must have the same
temperature/resistance curve as the other temperature sen-
sors on this unit. These sensors are 5,000 ohm at 75 F
(25 C).
OIL HEATER CONTACTOR (1C) This contactor is lo-
cated in the power panel and operates the heater at 115 v. It
is controlled by the PIC to maintain oil temperature during
machine shutdown.
OIL PUMP CONTACTOR (2C) This contactor is located
in the power panel. It operates all 200 to 575-v oil pumps.
The PIC energizes the contactor to turn on the oil pump as
necessary.
HOT GAS BYPASS CONTACTOR RELAY (3C)
(Optional) This relay, located in the power panel, con-
trols the opening of the hot gas bypass valve. The PIC en-
ergizes the relay during low load, high lift conditions.
Fig. 5 19EF Controls and Sensor Locations
9