Specifications

Table 9 LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. SHUTDOWN WITH ON/OFF/RESET-OFF
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
MANUALLY STOPPED PRESS CCN OR LOCAL TO START
PIC in OFF mode, press the CCN or local softkey to
start unit.
TERMINATE PUMPDOWN MODE TO SELECT CCN OR LOCAL
Enter the Control Test table and select Terminate Lockout to unlock com-
pressor.
SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING Machine unloading before shutdown due to Soft Stop feature.
SHUTDOWN IN PROGRESS COMPRESSOR DEENERGIZED
Machine compressor is being commanded to stop. Water pumps are
deenergized within one minute.
ICE BUILD OPERATION COMPLETE Machine shutdown from Ice Build operation.
B. TIMING OUT OR TIMED OUT
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
READY TO START IN XX MIN UNOCCUPIED MODE
Time schedule for PIC is unoccupied.
Machines will start only when occupied.
READY TO START IN XX MIN REMOTE CONTACTS OPEN Remote contacts have stopped machine. Close contacts to start.
READY TO START IN XX MIN STOP COMMAND IN EFFECT
Chiller START/STOP on Status01 manually forced to stop. Release
value to start.
READY TO START IN XX MIN RECYCLE RESTART PENDING Machine in recycle mode.
READY TO START UNOCCUPIED MODE
Time schedule for PIC is UNOCCUPIED. Machine will start when
occupied. Make sure the time and date have been set on the Serv-
ice menu.
READY TO START REMOTE CONTACTS OPEN Remote contacts have stopped machine. Close contacts to start.
READY TO START STOP COMMAND IN EFFECT
Chiller START/STOP on Status01 manually forced to stop. Release
value to start.
READY TO START IN XX MIN REMOTE CONTACTS CLOSED Machine timer counting down unit. Ready for start.
READY TO START IN XX MIN OCCUPIED MODE Machine timer counting down unit. Ready for start.
READY TO START REMOTE CONTACTS CLOSED Machine timers complete, unit start will commence.
READY TO START OCCUPIED MODE Machine timers complete, unit start will commence.
STARTUP INHIBITED LOADSHED IN EFFECT CCN loadshed module commanding chiller to stop.
READY TO START IN XX MIN START COMMAND IN EFFECT
Chiller START/STOP on Status01 has been manually forced to start.
Machine will start regardless of time schedule or remote contact status.
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RECYCLE RESTART PENDING OCCUPIED MODE
Unit in recycle mode, chilled water temperature is not high
enough to start.
RECYCLE RESTART PENDING REMOTE CONTACT CLOSED
Unit in recycle mode, chilled water temperature is not high
enough to start.
RECYCLE RESTART PENDING START COMMAND IN EFFECT
Chiller START/STOP on Status01 manually forced to start,
chill water temperature is not high enough to start.
RECYCLE RESTART PENDING ICE BUILD MODE
Machine in ICE BUILD mode. Chilled Water/Brine Tempera-
ture is satisfied for Ice Build Setpoint temperature.
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
PRESTART ALERT STARTS LIMIT EXCEEDED STARTS EXCESSIVE Compressor Starts (8 in
12 hours)
Depress the RESET softkey if additional start is
required. Reassess start-up requirements.
PRESTART ALERT HIGH MOTOR TEMPERATURE MTRW VALUE exceeded limit of [LIMIT]*.
Check motor temperature.
Check motor cooling line for proper operation.
Check for excessive starts within a short time
span. Check refrigerant filter.
PRESTART ALERT HIGH BEARING TEMPERATURE MTRB VALUE exceeded limit of [LIMIT]*. Check
thrust bearing temperature.
Check oil heater for proper operation, check for
low oil level, partially closed oil supply valves,
etc. Check sensor accuracy. Check oil cooler
and valve.
PRESTART ALERT HIGH DISCHARGE TEMP CMPD VALUE exceeded limit of [LIMIT]*. Check
discharge temperature.
Check sensor accuracy. Allow discharge tem-
perature to cool. Check for excessive starts. Avoid
entended low load operation.
PRESTART ALERT LOW REFRIGERANT TEMP ERT VALUE exceeded limit of [LIMIT]*. Check
refrigerant temperature.
Check transducer accuracy. Check for low chilled
water/brine supply temperature.
PRESTART ALERT LOW OIL TEMPERATURE OILT VALUE exceeded limit of [LIMIT]*. Check
oil temperature.
Check oil heater power, oil heater relay. Check
oil level. Check oil cooler solenoid.
PRESTART ALERT LOW LINE VOLTAGE V P VALUE exceeded limit of [LIMIT]*. Check
voltage suppy.
Check voltage supply. Check voltage transform-
ers. Consult power utility if voltage is low. Ad-
just voltage potentiometer in starter for SMM
voltage input.
PRESTART ALERT HIGH LINE VOLTAGE V P VALUE exceeded limit of [LIMIT]*. Check
voltage supply.
Check voltage supply. Check voltage transform-
ers. Consult power utility if voltage is low. Ad-
just voltage potentiometer in starter for SMM
voltage input.
PRESTART ALERT HIGH CONDENSER PRESSURE CRP VALUE exceeded limit of [LIMIT]*. Check
condenser water and transducer.
Check for high condenser water temperature.
Check transducer accuracy.
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert.
55