Specifications

When a safety shutdown occurs, the shutdown sequence
first stops the compressor by deactivating the start relay. A
status message of ‘SHUTDOWN IN PROGRESS, COM-
PRESSOR DEENERGIZED’is displayed. The guide vanes
are then brought to the closed position. The oil pump relay
and the chilled water/brine pump relay are shut down
60 seconds after the compressor stops. The condenser water
pump will be shut down when the CONDENSER REFRIG-
ERANT TEMP is less than the CONDENSER PRESSURE
OVERRIDE minus 5 psi (34 kPa) or is less than or equal to
the ENTERING CONDENSER WATER TEMP plus F
(2° C). The stop-to-start timer will now begin to count down.
If the start-to-start timer is still greater than the value of the
start-to-stop timer, then this time is now displayed on the
LID.
Certain conditions during shutdown will change this
sequence:
if the COMPRESSOR MOTOR LOAD is greater than 10%
after shutdown, or the starter contacts remain energized,
the oil pump and chilled water pump remain energized and
the alarm is displayed
if the ENTERING CONDENSER WATER temperature is
greater than 115 F (46 C) at shutdown, the condenser pump
will be deenergized after the 1CR compressor start relay
if the machine shuts down due to low refrigerant tempera-
ture, the chilled water pump will stay running until the
LEAVING CHILLED WATER is greater than CONTROL
POINT, plus F (3° C)
Automatic Soft StopAmps Threshold The SOFT
STOP AMPS THRESHOLD closes the guide vanes of the
compressor automatically when a non-recycle, non-alarm stop
signal occurs before the compressor motor is deenergized.
If the STOP button is pressed, the guide vanes close to a
preset amperage percent or until the guide vane is less than
2% open. The compressor will then shut off.
If the machine enters an alarm state or if the compressor
enters a RECYCLE mode, the compressor will be deener-
gized immediately.
To activate SOFT STOP AMPS THRESHOLD, view the
bottom of Service1 table. Set the SOFT STOPAMPS THRESH-
OLD value to the percentage amps at which the motor will
shut down. The default setting is 100% amps (no Soft Stop).
When the SOFT STOPAMPS THRESHOLD is being ap-
plied, a status message ‘SHUTDOWN IN PROGRESS, COM-
PRESSOR UNLOADING’ is shown.
Chilled Water Recycle Mode The machine may
cycle off and wait until the load increases to restart again
when the compressor is running in a lightly loaded condi-
tion. This cycling of the chiller is normal and is known as
recycle. A recycle shutdown is initiated when any of the fol-
lowing conditions are present:
when in LCW control, the LEAVING CHILLED WATER
temperature is more than F (3° C) below the control
point, and the CONTROL POINT has not increased in the
last 5 minutes
when ECW CONTROL OPTION is enabled, the ENTER-
ING CHILLED WATER temperature is more than F
(3° C) below the CONTROL POINT, and the CONTROL
POINT has not increased in the last 5 minutes
when the LEAVING CHILLED WATERtemperature is within
F (2° C) of the BRINE REFRIG TRIPPOINT
When the machine is in RECYCLE mode, the chilled wa-
ter pump relay remains energized so that the chilled water
temperature can be monitored for increasing load. The re-
cycle control uses RECYCLE RESTART DELTA T to check
when the compressor should be restarted. This is an operator-
configured function which defaults to F (3° C). This value
is viewed/modified on the Service1 table. The compressor
will restart when:
in LCW CONTROL the LEAVING CHILLED WATER tem-
perature is greater than the CONTROL POINT plus the RE-
CYCLE RESTART DELTA T; or
in ECW CONTROL, the ENTERING CHILLED WATER
temperature is greater than the CONTROL POINT plus the
RECYCLE RESTART DELTA T
Once these conditions are met, the compressor shall ini-
tiate a start-up, with a normal start-up sequence.
An alert condition may be generated if 5 or more RE-
CYCLE STARTUPs occur in less than 4 hours. This exces-
sive recycling can reduce machine life. Compressor recycling
due to extremely low loads should be reduced. To reduce
compressor recycling, use the time schedule to shut the ma-
chine down during low load operation or increase the ma-
chine load by running the fan systems. If the hot gas bypass
is installed, adjust the values to ensure that hot gas is ener-
gized during light load conditions. Increase the RECYCLE
RESTART DELTA T on the Service1 table to lengthen the
time between restarts.
The machine should not be operated below design
minimum load without a hot gas bypass installed on the
machine.
A—START INITIATED Prestart checks made; evaporator
pump started
B—Condenser water pump started (5 seconds after A)
C—Water flows verified (30 seconds to 5 minutes maximum
after B). Chilled water temperatures checked against con-
trol point. Guide vanes checked for closure. Oil pump started;
tower fan control enabled.
D—Oil pressure verified (15 seconds minimum, 300 seconds
maximum after C)
E—Compressor motor starts, compressor ontime and service
ontime start, 15-minute inhibit timer starts (10 seconds af-
ter D)
F—SHUTDOWN INITIATED Compressor motor stops, com-
pressor ontime and service ontime stops, and 1-minute in-
hibit timer starts.
G—Oil pump and evaporator pumps deenergized (60 seconds
after F). Condenser pump and tower fan control may con-
tinue to operate if condenser pressure is high. Evaporator
pump may continue if in RECYCLE mode.
O/A Restart permitted (both inhibit timers expired) (minimum of
15 minutes after E; minimum of 1 minute after F).
Fig. 22 Control Sequence
35