Specifications

20
Fig. 19 — Typical Piping for 09DK Condenser With a Dual Split System
*Field supplied.
NOTES:
1. Hot gas lines should rise above refrigerant level in
condenser circuit.
2. Trap should be installed on hot gas lines to prevent
condenser oil and refrigerant vapor migration from
accumulating on compressor heads during off cycle.
3. Pitch all horizontal lines downward in the direction of
refrigerant flow.
4. Refer to Carrier System Design Manual, part 3 for
proper piping sizes and design.
MOUNT TRANSDUCER TO LIQUID LINE
SERVICE VALVE USING TEE SUPPLIED IN KIT
CIRCUIT NO. 1
Fig. 20 — 38AH024-034 Unit Pressure Transducer Location