3.29 — Valve Plate Packages, Service Replacement
Carlyle began installing high efficiency valve plates in
the mid 1980’s. With a few exceptions noted, the valve
plates fit all current and older Carlyle compressors.
Check notes below the table for exceptions.
EGASUROSSERPMOCEGAKCAPETALPEVLAV
srosserpmoC)mfC14ot61(CC60,D60
,613RD60,313MD60,310RD60gnisufi(RD60.a
)2etoneessledom613MD60ro
,613RD606313MD60,310RD60gnisufi(AD,MD60.b
)2etoneessledom613MD60ro
egakcapevlavegatswol)mfC73ot61(CC60.c
egakcapevlavegatshgih)mfC73ot61(CC60.d
490066AD60
021066AD60
200066YC60
021066AD60
srosserpmoC)mfC99ot05(CC60,E60
RE60.a
AE,ME60.b
*evlavegatswol)mfC99ot05(CC60.c
evlavegatshgih)mfC99ot05(CC60.d
341066AE60
731066AE60
951066AE60
731066AE60
NOTES:
1. Carlyle recommends the 06ER660017 service replacement valve plate kit for all 06ER
compressors in low temperature environmental chamber applications (see Note 6).
2. All high efficiency (units with a “3” in the 11th digit of the model number) 06DR013 and
06DM313, 06DR316, and 06DM316 models have a 2" diameter cylinder bore and use the
above valve plate kits. Older 13 and 16 cfm (prior to 1985) models have a 1-13/16" diameter
bore and cannot use these valve plate kits. Kits for these models are no longer available.
Suction reed valve (part no. 6D45-1072) and discharge reed valve (part no. 6D75-1062) can be
used for valve plate field repair.
3. Hot gas bypass unloading requires a special valve plate kit with gaskets as follows:
06D.. ................06DA660131
06E ..................06EA660105
The Carlyle recommended suction cut-off unloading does not require a special valve plate.
Suction cutoff unloading uses the standard high efficiency valve plate kit, which includes the
needed gasket.
* Includes relief valve for both low stage banks.