Specifications

77
When the discharge gas temperature in the cylinder head
exceeds the sensor trip setting (see below), the sensor will
open the control circuit and shut off the compressor. The
head sensor must be wired into the control circuit by the
OEM and is pilot duty only at 240V = 0.52A, at 115V =
1.04A. The sensors are threaded into the head without a
well. Therefore, when changing a sensor, the compressor
must first be isolated and evacuated.
NOTES:
1. Since 1993 all Carrier 06 series air conditioning
compressors have been made without a sensor. All
Carlyle OEM 06 series compressors are equipped with
a sensor.
2. Starting in mid-1998 all Carlyle OEM compressors,
including 06EA, EM, ER and all 06CC models, are
built using the HN68GA295 sensor. The change to a
single sensor model is due to the increased use of HFC
refrigerants, which operate at lower temperatures.
3.16 — 06D, E Cylinder Head Cooling Fans
Cylinder head cooling fans are recommended on all
applications where the saturated suction temperature
(SST) is below 0°F (-18°C). A cylinder head cooling fan
must be used for all R-22 single stage applications
SNOITACIFICEPSERUTAREPMETDAEHREDNILYC
8991-dimot2891morfnoitaregirfeR
ZEdnaYE,ME,RE60rof
CC60dnaE60llA
srosserpmoC
rebmuNtraP
snepO
sesolC
roloCeriW
daerhT
3822150AE60
)C°4±°361(F°8±°523
)C°7±°121(F°21±°052
yerGrevliS
TPN"2/1
592AG86NH
)C°3±°641(F°5±°592
)C°311(muminimF°532
kcalB
TPN"2/1