Specifications
72
3.7 — Refrigerants and Oils for 06CC Compressors
All 06CC compressors are approved for R-22, R-404A
and R-507 except compressors in the 16 to 37 Cfm
range. Compressors in this size range cannot be used
with R-404A and R-507 prior to Serial No. 2099J ----
without installing a retrofit compressor valveplate (Part
No. 06CY660-002) kit. See Section 3.6 on page 69 for
further information about refrigerants and oils.
See Section 3.6 on page 71 for the correct oil for each
refrigerant. Contact Carlyle Engineering for correct oil
for R-23 and R-508A (SUVA 95).
3.8 — Oil and Refrigerant Change-Out Procedures
To change from a CFC or HCFC to either an HFC or an
HCFC blend, follow the refrigerant and oil manufacturer
installation procedures. Select a Carlyle approved
refrigerant and appropriate oil as noted in Sections 3.6
and 3.7 above. System cleanliness is extremely impor-
tant. To ensure a trouble-free change out, Carlyle
Engineering has made specific guidelines available. We
strongly recommend a copy of our guidelines be re-
quested and procedures carefully followed to avoid
problems.
3.9 — Oil Viscosity and Pour Points
The viscosity of oils used in Carlyle reciprocating
compressors is ISO 68 (centistoke) for all POE oils and
150 Saybolt Seconds Universal (150 SSU or 150 SUS)
or ISO 32 for mineral and alkylbenzene oils. Using oil
with a different viscosity without approval from the
Carlyle Engineering Department will void the warranty.
The oils listed in Sections 3.6 and 3.7 and the viscosity
listed above can be used down to -40°F (-40°C). If your
system runs at a lower temperature, please contact
Carlyle Engineering for an oil recommendation.