Specifications

34
4. Pry up along sides of valve plate to remove valve plate
from crankcase. This provides access to suction reed
valves (see Fig. 3). Remove suction valves from dowel
pins. On 06D and 06CC (16 to 37 Cfm) compressors,
also remove the suction valve positioning springs (see
Fig. 4).
5. Inspect components for wear or damage. If replacement
is necessary, replace as a complete assembly. Individual
parts must not be interchanged. Alignment of high
efficiency discharge valves is critical for proper seating.
See Sections 3.27 to 3.29, pages 84-87 for applicable
replacement valve plate packages.
Fig. 2 –– Disassembly of Valve Plate
(Standard Efficiency Valve Plate Shown)