Specifications
15
Use only Carlyle approved oil appropriate for the
refrigerant being used. Sections 3.6 and 3.7 on
pages 69-72 list all the approved oils. Section 3.11 on
page 73 notes the correct oil pump pressure in relation to
age of the compressor.
3. Leak test, evacuate, and dehydrate the system.
4. Charge the system. When initially charging the high side
of the system with liquid refrigerant, all service valves
should be closed (front seated). This will prevent
refrigerant from migrating to the compressor crankcase
and into the oil, causing a flooded start.
The system is now charged and ready for start-up.
Recheck the oil levels and add or remove oil as neces-
sary. Open (backseat) the discharge service valve and
any oil equalization lines on parallel systems. Open the
suction service valve 1/2 to 1 turn, or enough to allow
the compressor to run without tripping the low-pressure
switch. This is to prevent damage to the compressor
from any liquid refrigerant floodback.
5. On water-cooled condensing systems, open water supply
valve and allow water to reach condenser. On air-cooled
condensing systems, turn condenser fan on when the
compressor unit is started.
6. Ensure that all evaporator connections are opened and
fans started.
7. On systems with more than one compressor in parallel,
start one compressor at a time.