Specifications

101
LEGEND:
LRA - Locked Rotor Amps
M.H. - Must Hold Amps
M.T. - Must-Trip Amps
PW - Part-Winding (Start)
RLA - Rated Load Amps
XL - Across-the-Line (Start)
NOTES:
1.
Compressor must-trip (M.T.) amps and RLA values are maximum figures.
2. LRA values for PW second winding = 1/2 the LRA -XL value.
3. 3-Pole XL circuit breakers shown, other 3-Pole XL alternates and 6-Pole PW breakers available. Terminal lugs for circuit br
eakers available in
package 06EA660152.
4. Recommended RLA value shown is determined by: circuit breaker must trip value
÷
1.40. Use this recommended (and minimum) RLA value to
determine name plate stamping, minimum contactor sizing, and wire sizing. RECOMMENDED RLA FOR 06E COMPRESSORS EQUALS:
MUST-TRIP (M.T.) OF CARLYLE APPROVED OVERCURRENT DEVICE BEING USED
÷
1.40.
5. 06EM266
New OEM Models no longer produced, replaced by 06EA265.
6. Compressor operating amps at any specific condition can only be determined from a performance curve.
7. Ohm values for resistance are approximate and shown for reference purposes only. Motors from different vendors and motors o
f different efficiencies
can differ up to 15% from data shown.