Operating instructions

Rexroth IndraDrive Mounting and Installation 6-11
DOK-INDRV*-FU*********-IB01-EN-P
Mains Choke U
N
[V]
I
N
[A]
L
N
[µH]
P
V
[W]
I
max
[A]
L
min
at I
max
Connection
Cross Section
[mm²]
HNL01.1E-1000-N0012-A-500-NNNN 500 12 3 x 1000 40 25 50% of L
N
4 (a, b: 4)
HNL01.1E-1000-N0020-A-500-NNNN 500 20 3 x 1000 60 50 50% of L
N
6 (a, b: 4)
HNL01.1E-0600-N0032-A-500-NNNN 500 32 3 x 600 75 80 50% of L
N
10 (a, b: 4)
HNL01.1E-0571-N0050-A-500-NNNN 500 50 3 x 571 50 100 50% of L
N
16 (a, b: -)
AWG 8
HNL01.1E-0400-N0051-A-480-NNNN 480 51 3 x 400 165 77 50% of L
N
16 (a, b: 2,5)
HNL01.1E-0362-N0080-A-500-NNNN 500 80 3 x 362 80 160 50% of L
N
35 (a, b: -)
AWG 6
HNL01.1E-0240-N0106-A-500-NNNN 500 106 3 x 240 100 212 50% of L
N
35 (a, b: -)
AWG 1/0
HNL01.1E-0200-N0125-A-480-NNNN 480 125 3 x 200 170 188 50% of L
N
70 (a, b: 2,5)
HNL01.1E-0170-N0146-A-500-NNNN 500 146 3 x 170 130 292 50% of L
N
50 (a, b: -)
AWG 1/0
HNL01.1E-0100-N0202-A-480-NNNN 480 202 3 x 100 200 303 50% of L
N
150 (a, b: 2,5)
Fig. 6-11: Electrical data HNL
Temperature Contact a, b
1 A / AC 250 V; DC 24 V
125 °C
Note: HNL01.1E mains chokes of type 1 are equipped with a
temperature contact (a, b), types 2, 3 and 4 are not.
Switching Capacity
Switching Temperature