Operating instructions
5-26 Electrical Data Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
Motor Filter HMF
Motor filter I
N
[A]
P
V
[W]
L
M
[µH]
f
out_max
[Hz]
f
p_max
[kHz]
du/dt at
output
[kV / us]
U
out_max
[kV]
HMF01.1A-N0K2-D0045-A-500-NNNN 45 120 3 x 160 200 4 < 1 1,2
HMF01.1A-N0K2-D0073-A-500-NNNN 73 160 3 x 100 200 4 < 1 1,2
HMF01.1A-N0K2-D0095-A-500-NNNN 95 190 3 x 78 200 4 < 1 1,2
HMF01.1A-N0K2-D0145-A-500-NNNN 145 220 3 x 50 200 4 < 1 1,2
Fig. 5-37: Electrical data
Motor filter Cross section
[mm²]
Cross section
flexible
[mm²]
Cross section
[AWG]
Tightening
torque
[Nm]
HMF01.1A-N0K2-D0045-A-500-NNNN 16 - 6 1,5
HMF01.1A-N0K2-D0073-A-500-NNNN 35 - 2 6
HMF01.1A-N0K2-D0095-A-500-NNNN 50 2*25 0 6
HMF01.1A-N0K2-D0145-A-500-NNNN 95 2*50 4/0 25
Fig. 5-38: Terminal connector data