Operating instructions
5-14 Electrical Data Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
Analog Output Type 3
Data Unit Min. Typ. Max.
output voltage V -10 +10
output load kOhm 1
output current mA 0 +1
converter width digital/analog
converter incl. polarity sign
Bit 12
resolution mV/Ink 5
accuracy at R = 1 kOhm % 1 of FMR
accuracy at R = 10 kOhm % 0,2 of FMR
conversion time
(incl. response time)
us 10
cyclic conversion us depending on firmware
short circuit protection present
overload protection present
FMR: final value of measuring range
Fig. 5-23: Analog outputs type 3