Operating instructions

5-6 Electrical Data Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
5.2 Control Sections
Relay Contact Type 1
Data Unit Min. Typ. Max.
current load capacity A DC 1
AC 2
voltage load capacity V DC 30
AC 250
minimum contact load mA 10
contact resistance at
minimum current
mOhm 1000
switching actions at max. time
constant of load
100.000
number of mechanical
switching cycles
1 * 10
6
time constant of load ms 50
pick up delay ms 10
drop out delay ms 10
Fig. 5-6: Relay contacts type 1
Relay Contact Type 2
Data Unit Min. Typ. Max.
current load capacity A DC 1
voltage load capacity V DC 30
minimum contact load mA 10
contact resistance at
minimum current
mOhm 1000
switching actions at max. time
constant of load
1 * 10
6
number of mechanical
switching cycles
1 * 10
8
time constant of load ms ohmic
pick up delay ms 10
drop out delay ms 10
Fig. 5-7: Relay contacts type 2