Operating instructions

Rexroth IndraDrive Electrical Data 5-3
DOK-INDRV*-FU*********-IB01-EN-P
CSB01.1N-FC… I
EIN3
A 1,5 (pulse width t
EIN3lade
ca. 120 ms)
CSB01.1N-PB… I
EIN3
A 5 (pulse width t
EIN3lade
ca. 40 ms)
Power consumption of optional modules according to type code 3), 4)
CP
N3
W1,0
EN1 P
N3
W6,0
EN2 P
N3
W5,5
ENS P
N3
W5,5
MA1 P
N3
W2,0
MD1 P
N3
W1,0
SP
N3
W1,0
1) plus control section with optional modules
2) plus optional modules
3) code from the control section type code
4) at max. allowed output load without circuits to be supplied externally
Fig. 5-2: Control voltage
Power Voltage Supply- Mains Connection
Designation Symbol Unit HCS02.1E HCS03.1E
allowed range of mains input
voltage, three-phase;
TN-S, TN-C, TT mains
U
LN
V
3 * AC (200…500)
+-10%
3 * AC (400…500)
+10% -15%
allowed range of mains input
voltage, three-phase;
IT mains
U
LN
V
3 * AC (200…230)
+-10%
not allowed
allowed range of mains input
voltage, single-phase
U
LN
V 1 * AC (200…250) +-10% not allowed
rotary field no rotary field condition
allowed range of mains
frequency
f
LN
Hz (50…60) + - 2
max. allowed mains frequency
change
d f
LN
/t Hz/s 2% * f
LN
Fig. 5-3: Extended range of power voltage
Note: When using HCS02 and HCS03 devices in the mains voltage
range up to 3 * AC 500 V, make sure the additional
components you use may be operated in this mains voltage
range. NFD mains filters, for example, can only be used up to
3 * AC 480 V.