Operating instructions
Rexroth IndraDrive Electrical Data 5-1
DOK-INDRV*-FU*********-IB01-EN-P
5 Electrical Data
5.1 Power Sections
Unless otherwise specified, the following data apply to
• T
a
= T
amax
• U
LN
= 3AC400V
• use of HNL and HNK mains chokes
Type Current and Connected Load
Compact
converter
Type
current
Attached mains choke
HNL, HNK
Nominal
motor
power
(2)
Connec-
ted load
Mains
input
contin.
current
Nominal fuse
current / fuse
type
character-
istic gL
Contin.
current
(1)
Peak
current
(1)
S
LN
I
L_cont
Type I
out_cont1
I
out_max
[kW] [kVA] [A] [A] [A] [A]
HCS02 W0012 HNL01.1E-1000-N0012 1,5 3,5 6 10 4 12
HCS02 W0028 HNL01.1E-1000-N0012 4,0 7,3 13 20 11 28
HCS02 W0054 HNL01.1E-1000-N0020 7,5 13,3 19 25 22 54
HCS02 W0070 HNL01.1E-0600-N0032 11 18,5 30 35 28 70
HCS03 W0070 HNL01.1E-0571-N0050
HNK01.1A-A075-E0080
18,5 35 50 3NA6820-4 45 70
HCS03 W0100 HNL01.1E-0362-N0080;
HNK01.1A-A075-E0080
30 55,2 80 3NA6824-4 73 100
HCS03 W0150 HNL01.1E-0240-N0106
HNK01.1A-A075-E0106
45 72,9 106 3NA6832-4 95 150
HCS03 W0210 HNL01.1E-0170-N0146
HNK01.1A-A075-E0146
75 99,3 146 3NA6836-4 145 210
(1) at f
s
= 4 kHz; without overload
(2) for standard motor, when using mains choke HNL01; at 3 AC 400 V
variable torque, low overload
Fig. 5-1: Type current and connected load