Operating instructions
4-8 Identification, Transport, Storage, Installation Conditions Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
Capacity Utilization
Where installation conditions differ, the following performance data are
reduced in accordance with the diagrams (see "Fig. 4-15: " and "Fig. 4-16:
"):
drive controller:
• allowed continuous DC bus power
• continuous power of braking resistor
• continuous current
motor:
• power
• continuous torque at standstill
• S1 continuous torques
• short-time service torque MKB
If differing ambient temperatures and higher installation altitudes occur
simultaneously, both capacity utilization factors must be multiplied. The
installation altitude must only be taken into account once, deviating
ambient temperatures must be taken into account separately for motor
and drive controller.
DK000073v01_en
0,7
1
40 45 50 55
5
Load factor
Ambient temperature in °C
Fig. 4-15: Capacity utilization at higher ambient temperature