Operating instructions

7-126 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
Voltage-controlled operation (U/f)
S-0-0106, Current loop proportional gain 1
S-0-0107, Current loop integral action time 1
P-0-0532, Premagnetization factor
P-0-0568, Voltage boost
P-0-0569, Maximum stator frequency change
P-0-0570, Stall protection loop proportional gain
P-0-0571, Stall protection loop integral action time
P-0-0572, Slip compensation factor
P-0-0573, IxR boost factor
P-0-0574, Oscillation damping factor
P-0-0575, Search mode: search current factor
P-0-0576, Search mode: finding point slip factor
P-0-0577, Square characteristic: lowering factor
Fig. 7-58: Overview of motor control parameters for synchronous and
asynchronous motors
Determining Parameters by Means of Type Plate Data
For asynchronous motors it is possible via C3200 Command Calculate
motor data to calculate the values for motor parameters from the type
plate data and then the values of the motor control parameters. The
activation of C3200 first requires manual input of the motor data from the
type plate of the asynchronous motor in parameter P-0-4032, Motor type
plate data.
See Parameter Description "P-0-4032, Motor type plate data"
Note: The command C3200 can only be used for asynchronous
motors and can only be activated in communication phases
"P2" or "P3"!
The figure below illustrates the scope of functions of the command
C3200:
Command "Calculate motor
data" (C3200)