Operating instructions

7-110 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
When switching on the 24 V supply voltage an automatic protocol
detection is activated when receiving signals via the serial interface.
A soon as either
a valid ASCII start sequence
- or -
a valid SIS telegram
was received the drive internally switches to the respective kind of
protocol.
transmission rates of 9600 and 19200 baud
8-bit ASCII protocol
no parity bit
one stop bit
Note: There isn't any telegram frame used but the transmitted ASCII
signs are converted and interpreted. It is only necessary to
comply with a certain order.
binary protocol
checksum test (higher Hamming distance D)
all telegrams are identified by an unequivocal start character ("0x02")
defined structure of the telegram frame
it is possible to activate motions (e.g. jogging)
Master Communication
General
address assignment
communication address to be freely parameterized (via master
communication, serial and control panel) via parameter P-0-4025,
Drive address of master communication
Baud rate PROFIBUS-DP
P-0-4079, Field bus: Baud rate
The baud rate used by the field bus is automatically determined and only
displayed in this parameter.
Note: By inputting "0" as baud rate it is possible to activate automatic
baud rate detection. In some cases this however might not
work correctly so that it is recommended to make a manual
input.
Open Loop
In operation without encoder (open-loop operation) the velocity control
loop is not closed in the drive, but the drive is operated in a velocity-
controlled way (without feedback) via open-loop U/f control.
Note: The method of open-loop/closed-loop motor control can be
selected via bit
14 of parameter P-0-0045, Control word of
current controller
.
Properties of ASCII Protocol
Properties of SIS Protocol