Operating instructions

7-108 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
The effects of the command S-0-0262, C07_x Load defaults procedure
command depend on the configuration available in P-0-4090 at the
command start.
See also Functional Description "Loading Default Values"
See also Parameter Description "S-0-0262, C07_x Load defaults
procedure command"
P-0-4091, C2500 Copy IDN from optional memory to
internal memory
Input min/max: Default value: Unit:
MPB: --- / --- --- --
By means of this command the parameter values are copied from the
MultiMediaCard (MMC) to the internal, non-volatile memory (flash).
P-0-4092, C2600 Copy IDN from internal memory to
optional memory
Input min/max: Default value: Unit:
MPB: --- / --- --- --
By means of this command the parameter values are copied from the
internal, non-volatile memory (flash) to the MultiMediaCard (MMC).
P-0-4095, RS-232/485 Parity
Input min/max: Default value: Unit:
MPB: 0 / 2 0 --
By means of this parameter it is possible to set several parities for the
communication via the serial interface.
Parity Setting in P-0-4095
none 0
odd 1
even 2
Fig. 7-48: Coding of the parity in P-0-4095
The initial setting is no parity (default value).
See also Functional Description "Serial Communication"
7.4 Basic Functions
Serial Communication
The serial interface of the drive controller is used as a universal medium
of communication for different services. It can be used for master
communication (in addition to SERCOS), for reading and writing
Function
Function
Function
Function