By means of this parameter the proportional gain of the voltage loop is
entered. The voltage loop is used to control the motor voltage in the field-
weakening range.
Note:
Writing the correct value to this parameter:
In the case of MAD and MAF with encoder data memory
automatically during initial commissioning.
In the case of 2AD, ADF, linear and rotary kit motors, by
loading the motor parameters with the commissioning
software (e.g. IndraWorks).
In the case of other motors: default value or manual input.
See also Functional Description "Third-Party Motors at IndraDrive
Controllers"
P-0-0534, Voltage loop integral action time
Input min/max: Default value: Unit:
MPB: 0,0 / 429496729,5 600,0 ms
By means of this parameter the integral action time of the voltage loop is
entered. The voltage loop is used to control the motor voltage in the field-
weakening range.
Note:
Writing the correct value to this parameter:
In the case of MAD and MAF with encoder data memory
automatically during initial commissioning.
In the case of 2AD, ADF, linear and rotary kit motors, by
loading the motor parameters with the commissioning
software (e.g. IndraWorks).
In the case of other motors: default value or manual input.
See also Functional Description "Determining the Motor Parameter
Values"
P-0-0535, Motor voltage at no load
Input min/max: Default value: Unit:
MPB: 0,0 / 100,0 80,0 %
As a matter of principle, this parameter only takes effect in field
weakening operation. It defines a voltage that is indicated in percent of
the maximum converter output voltage.
See also Functional Description "Determining the Motor Parameter
Values"
P-0-0536, Maximum motor voltage
Input min/max: Default value: Unit: