Operating instructions
Rexroth IndraDrive Commissioning and Parameterization 7-75
DOK-INDRV*-FU*********-IB01-EN-P
See also Functional Description "Analog Outputs"
P-0-0426, Analog output IDN list of assignable
parameters
Input min/max: Default value: Unit:
MPB: --- / --- --- --
This parameter contains a list of all parameter IDNs that can be assigned
via
• P-0-0420, Analog output, assignment A, signal selection and
• P-0-0423, Analog output, assignment B, signal selection
See also Functional Description "Analog Outputs"
P-0-0427, Control parameter of analog output
Input min/max: Default value: Unit:
MPB: --- / --- --- --
This configuration parameter determines the signal source and conditions
for the analog outputs.
See also Functional Description "Analog Outputs"
P-0-0440, Actual output current value (absolute value)
Input min/max: Default value: Unit:
MPB: --- / --- --- A eff
Display parameter for the measured actual current value which is the rms
value of the motor phase current.
The phase currents are scanned in the current controller cycle, converted
as a current vector and the rms value is calculated from these data. This
parameter displays the value averaged during 2 ms and is used as the
input value for the overload models of amplifier and motor.
P-0-0441, Overload warning
Input min/max: Default value: Unit:
MPB: 0 / 100 80 %
Parameter for determining a threshold value for thermal controller work
load.
If the value displayed in P-0-0141, Thermal drive load exceeds the
determined threshold, the warning E2061 Amplifier overload
prewarning is generated.
The unit of the threshold value corresponds to the one of P-0-0141 (%).
Note: When 100% is entered, E2061 Amplifier overload
prewarning is not displayed. Instead, the warning E8057
Amplifier overload, current limit active is already generated
with approx. 97% of the thermal work load.
Function
Function
Function
Function