Operating instructions
7-74 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
By means of this parameter it is possible to assign a parameter IDN to the
analog outputs 1 and 3 of the drive controller. The current parameter
value is output as voltage at the analog output, if the mode of the analog
output in P-0-0427, Control parameter of analog output has been set to
output of assignment A. The output voltage can be made visible with an
oscilloscope, for example.
It is only possible to assign those IDNs that have been entered in the
P-0-0426, Analog output IDN list of assignable parameters list.
See also Functional Description "Analog Outputs"
P-0-0422, Analog output, assignment A, scaling [1/V]
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
This parameter is used to scale the voltage output by analog output 1 and
3. The unit is determined by the parameter assigned in P-0-0420, Analog
output, assignment A, signal selection.
When assigning parameters with the "binary" display attribute, the number
of the bit to be output at the analog output is defined in this parameter.
When the respective bit has not been set, the output voltage is 0 V. When
the bit has been set, 1 V is output.
See also Functional Description "Analog Outputs"
P-0-0423, Analog output, assignment B, signal selection
Input min/max: Default value: Unit:
MPB: --- / --- --- --
By means of this parameter it is possible to assign a parameter IDN to the
analog outputs 2 and 4 of the drive controller. The current parameter
value is output as voltage at the analog output, if the mode of the analog
output in P-0-0427, Control parameter of analog output has been set to
output of assignment B. The output voltage can be made visible with an
oscilloscope, for example.
It is only possible to assign those IDNs that have been entered in the
P-0-0426, Analog output IDN list of assignable parameters list.
See also Functional Description "Analog Outputs"
P-0-0425, Analog output, assignment B, scaling [1/V]
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
This parameter is used to scale the voltage output by analog output 2 and
4. The unit is determined by the parameter assigned in P-0-0423, Analog
output, assignment B, signal selection.
When assigning parameters with the "binary" display attribute, the number
of the bit to be output at the analog output is defined in this parameter.
When the respective bit has not been set, the output voltage is 0 V. When
the bit has been set, 1 V is output.
Function
Function
Function
Function