Operating instructions

Rexroth IndraDrive Commissioning and Parameterization 7-71
DOK-INDRV*-FU*********-IB01-EN-P
Note: Apart from the IDN, the bit number desired for the input or
output (cf. P-0-0301, Digital I/Os, bit numbers) and the
output direction (cf. P-0-0302, Digital I/Os, direction) have to
be defined!
See also Functional Description "Digital Inputs/Outputs"
P-0-0301, Digital I/Os, bit numbers
Input min/max: Default value: Unit:
MPB: --- / --- --- --
This parameter is used to configure the digital inputs/outputs of the
control section.
In P-0-0301, Digital I/Os, bit numbers the desired bit number which is to
be assigned to the digital input or output is indicated for each assigned
parameter (cf. P-0-0300, Digital I/Os, assignment list).
Note: Apart from determining the bit number, the IDN desired for the
output or input has to be defined via P-0-0300, Digital I/Os,
assignment list.
See also Parameter Description "P-0-0300, Digital I/Os, assignment list"
See also Functional Description "Digital Inputs/Outputs"
P-0-0302, Digital I/Os, direction
Input min/max: Default value: Unit:
MPB: --- / --- --- --
This parameter is used to configure the digital inputs/outputs of the
control section.
In parameter P-0-0302, Digital I/Os, direction the desired function
(direction) is indicated for each assigned parameter (cf. P-0-0300, Digital
I/Os, assignment list). This means that parameter P-0-0302 sets the
digital input or output.
"0" for "input" function
"1" for "output" function
Note: Apart from determining the "digital I/Os, direction", the desired
IDN and bit number for the output or input has to be defined
via P-0-0300, Digital I/Os, assignment list or P-0-0301,
Digital I/Os, bit numbers.
See also Functional Description "Digital Inputs/Outputs"
P-0-0303, Digital I/Os, status display
Input min/max: Default value: Unit:
MPB: --- / --- --- --
Function