Operating instructions

7-66 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
See also Functional Description "Analog Inputs"
P-0-0217, Analog input 1, time constant input filter
Input min/max: Default value: Unit:
MPB: 0,250 / 60,000 0,250 ms
The analog input 1 can be read by the drive firmware via a digital low-
pass filter. The limit frequency of this filter is set by this parameter, if
necessary the filter can also be deactivated.
f
limit
= 1000 / (2 *
π
* T
input.
)
f
limit
: limit frequency in Hz
T
input.
: time constant of input filter in ms
Fig. 7-43: Calculating the limit frequency of the analog input filter
Performance (P-0-0556) Input filter T
input
in µs
inactive 500 µsstandard (bit 2 = 0)
active >500 µs
inactive 250 µshigh (bit 2 = 1)
active >250 µs
Fig. 7-44: Settings of the analog input filter
See also Functional Description "Analog Interface"
See also Functional Description "Analog Inputs"
P-0-0218, Analog input, control parameter
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
This parameter is used
for controlling the command "analog input adjust"
for assigning the analog channels for "assignment analog channel A"
or "assignment analog channel B"
for selecting current input or voltage input
for selecting the measuring range
for selecting the kind of reaction in the case of wire break
Note: It is possible to adjust both analog voltage and current inputs!
See also Functional Description "Analog Interface"
See also Functional Description "Analog Inputs"
P-0-0219, Analog input, maximum value for adjust
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
Function
Function