7-46 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
See also Functional Description "Motor Temperature Monitoring"
S-0-0204, Motor shutdown temperature
Input min/max: Default value: Unit:
MPB: 155,0 S-0-0208
If the motor temperature exceeds the motor shutdown temperature, the
drive sets bit 2 (motor overtemperature shutdown) in S-0-0011, Class 1
diagnostics and the error F2019 Motor overtemperature shutdown is
generated.
In the case of MHD and MKD motors, the drive sets this parameter to
155 °C, in the case of MKE motors to 135 °C.
See also Functional Description "Motor Temperature Monitoring"
S-0-0208, Temperature data scaling type
Input min/max: Default value: Unit:
MPB: --- / --- 0 --
By means of this parameter the unit of the temperature data of the drive is
determined. The values are displayed with the first decimal place.
S-0-0265, Language selection
Input min/max: Default value: Unit:
MPB: 0 / var. 0 --
All parameter names, units and diagnostic/error messages are stored in
the drive controller in several languages. This parameter determines the
language of the texts to be output.
• 0: German
• 1: English
• 2: French
• 3: Italian
• 4: Spanish
See also Functional Description "Language Selection"
S-0-0292, List of all operating modes
Input min/max: Default value: Unit:
MPB: --- / --- --- --
All operating modes that are supported by the drive firmware used are
listed in this parameter.
The codes (hexadecimal) of those operating modes are displayed that
can be entered in the parameters S-0-0032 … S-0-0035 and
S-0-0284 … S-0-0287 (primary mode of operation and secondary
operation modes) in the form of binary values.
See also Functional Description "Operating Modes"