Operating instructions

Rexroth IndraDrive Commissioning and Parameterization 7-35
DOK-INDRV*-FU*********-IB01-EN-P
Fig. 7-35: Error message when switching operating mode/parameter mode
Switch off drive enable and repeat procedure.
Select Save/Load parameters
Press key
.
Following display appears:
Fig. 7-36: Parameter management
Press Prog
+
key.
At start of process, Start Restore is displayed (see following figure)
and parameter set is loaded to drive controller. At the same time,
number of bytes already loaded is displayed. By means of numbers,
Progress shows you current status of process (on the right there is
the end number; to the left of the end number there is the current
number).
Data Restored indicates successful end of process.
If an error occurred, the corresponding message is displayed in lowest
line. In this case you have to remove error first and then restart
process.
ErrCode: Displayed only in the case of an error (e.g. "Err at Init")
Fig. 7-37: Load parameters