Operating instructions
7-34 Commissioning and Parameterization Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
• Press Mon key.
At start of process, Start Save is displayed (see following figure) and
parameter set is copied to comfort control panel. At the same time,
number of bytes already copied is displayed. By means of numbers,
Progress shows you current status of process (on the right there is
the end number; to the left of the end number there is the current
number).
Data Saved indicates successful end of process.
If an error occurred, the corresponding message is displayed in lowest
line. In this case you have to remove error first and then restart
process.
ErrCode: Displayed only in the case of an error (e.g. "Err at Init")
Fig. 7-33: Save parameters
• Plug comfort control panel with copied parameter set on drive
controller to which parameter set is to be loaded.
• Reboot drive controller with comfort control panel plugged.
• Go to main screen.
By pressing key
several times you get to main screen. By means of
Esc key, you might possibly have to exit editing mode before.
• Press key
.
Mode selection is displayed.
• Select Parameter management
• Press key
.
Parameter mode is automatically displayed. Following display appears:
Fig. 7-34: Parameter management
When drive controller was in status AF (drive enable), following display
appears:
Load Parameters