Operating instructions

Rexroth IndraDrive Commissioning and Parameterization 7-21
DOK-INDRV*-FU*********-IB01-EN-P
Up to 8 arbitrary parameters can be displayed. The parameters can be
displayed successively. Parameter P-0-4024 contains the IDNs of the
parameters which can be selected for cyclic parameter display.
Presetting of list in P-0-4024:
List element Listed IDN
0 S-0-0040 Velocity feedback value
1 S-0-0084 Torque/force feedback value
2 P-0-0043 Torque-generating current, actual value
3 S-0-0382 DC bus power
4 S-0-0000 dummy ID
5 S-0-0000 dummy ID
6 S-0-0000 dummy ID
7 S-0-0000 dummy ID
Fig. 7-12: Presetting of list in P-0-4024
The "dummy" S-0-0000 will be ignored during configuration, i.e. only
entries with valid IDNs are displayed (in this case: entries in list elements
0…3).
From each display you can go to setting of list parameter P-0-4024 by
pressing
key.
Select IDN in table by pressing
or key.
Modify IDN.
Press Enter key.
Press Esc key.
Press
key to restart cyclic parameter display.
At first, list entries are checked. Then first parameter of list is
displayed. Top right you see number of list element displayed.
Fig. 7-13: Example of the first list element displayed
Press key to go to next list element.
Press
key to go to previous list element.
Press Esc key to leave the Cyclic Parameter List Display
Cyclic Parameter List Display