Operating instructions
6-58 Mounting and Installation Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
Cable Routing to the Right:
CAUTION
Damage caused by voltage arcing!
Insulate ring terminals and connecting lines with a
heat-shrinkable sleeve. Afterwards only strip the
insulation of the contact surface of the ring terminal.
DC bus nach rechts_1f4.fh7
correct incorrect
device 1
(DC bus connection)
device 2
(DC bus connection)
device 1
(DC bus connection)
device 2
(DC bus connection)
Fig. 6-81: DC bus connections for cable routing to the right
Connection Point of Equipment Grounding Conductor
and Equipment Grounding Connections
DANGER
Dangerous contact voltage at device housing!
Lethal electric shock!
Connect the drive controller to the equipment
grounding system via connection X3 (mains).
Ground Connection of Housing
The ground connection of the housing is used to provide functional safety
of the drive controllers and protection against contact in conjunction with
the equipment grounding conductor.
Ground the housings of the drive controllers:
1. Connect the bare metal back panel of the drive controller in
conductive form to the mounting surface in the control cabinet. To do
this use the supplied mounting screws.
2. Connect the mounting surface of the control cabinet in conductive
form to the equipment grounding system.