Operating instructions

6-46 Mounting and Installation Rexroth IndraDrive
DOK-INDRV*-FU*********-IB01-EN-P
Connect cable shield to a ground bus. The maximum distance between
ground bus and device connection is 100 mm. For this purpose take the
given length of the single strands at the cable end into account for ready-
made Rexroth motor power cables.
motorkabel_schirmauflage_b.fh7
2
3
1
56
4
7
1: drive controller
2: clip for shield contact
3: overall shield of the motor power cable folded back
4: ground bus in control cabinet
5: single strands of motor power cable
6: connection of ground bus to supplying device
7: strain relief (as near as possible to control cabinet outlet)
Fig. 6-58: Shield contact, alternative 1
With a clip (2) connect overall shield of motor power cable (3) to
ground bus (4).
(If you use your own cable make sure the shields of the two inner
pairs of wires are in contact with the overall shield.)
With a cable (6) (line cross section at least 10 mm
2)
connect ground
bus (4) to ground connection at supplying device (Rexroth IndraDrive
supply unit or Rexroth IndraDrive drive controller HCS).
Alternative 1