Operating instructions

Rexroth IndraDrive Mounting and Installation 6-43
DOK-INDRV*-FU*********-IB01-EN-P
HCS03.1E- Cross section
single-wire
[mm²]
Cross section
multi-wire
[mm²]
Cross section
in AWG
W0070 16 - 6
W0100 35 - 2
W0150 50 2*25 0
W0210 95 2*50 4/0
Fig. 6-47: Connection cross section
HCS02.1E- Tightening torque [Nm]
W0012, W0028 0,5 – 0,6
W0054, W0070 1,2 – 1,5
Fig. 6-48: Tightening torques
HCS03.1E- Tightening torque [Nm]
W0070 1,5
W0100, W0150 6
W0210 25
Fig. 6-49: Tightening torques
CAUTION
Damage to the drive controller
Strain relief for the motor power cable must be
provided within the control cabinet, or you can use
the optionally available connection accessory
HAS02.1.
Note: Observe the following for use within the scope of C-UL:
Use 60/75 °C copper wire only
Use Class 1 wire only or equivalent
Suitable for use on a circuit capable of delivering not more
than 8 kA (10 kA) rms symmetrical amperes for a
maximum voltage of 500 V (400 V)
X5, Motor Connection
DANGER
High electrical voltage! Danger to life, severe
bodily harm by electric shock!
Always operate the drive controller with plugged on
connector!
HCS02.1E- Type No. of
poles
Type of design
W0012..0070 Screw terminal
block
4 Pins on device
Fig. 6-50: Design
Tightening Torque
Design