Operating instructions

Rexroth IndraDrive Mounting and Installation 6-35
DOK-INDRV*-FU*********-IB01-EN-P
Installing the 24V Supply
As a matter of principle, the 24V supply of the components of the drive
system Rexroth IndraDrive has to be installed in star-shaped form, i.e. for
each group of drive controllers or third-party components it is necessary
to run separate supply lines. This, too, applies to multiple-line
arrangement in the case of supply from a supply unit, for example.
DA000006v01_nn
HCS02
HCS02
1)
HMV
HMS
HMD
2)
PE
24V
1) third-party component (e.g. PLC, valve etc.)
2) connection to central ground point (e.g. earth-circuit connector)
Fig. 6-34: Installing the 24V supply
Note: If you use several power supply units for 24 V supply, make
sure that
the reference conductors 0V of the individual power supply
units are interconnected with low impedance
the output voltages of the power supply units are within the
allowed voltage range
the power supply units are synchronously switched on and off.