Operating instructions
Rexroth IndraDrive Mounting and Installation 6-35
DOK-INDRV*-FU*********-IB01-EN-P
Installing the 24V Supply
As a matter of principle, the 24V supply of the components of the drive
system Rexroth IndraDrive has to be installed in star-shaped form, i.e. for
each group of drive controllers or third-party components it is necessary
to run separate supply lines. This, too, applies to multiple-line
arrangement in the case of supply from a supply unit, for example.
DA000006v01_nn
HCS02
HCS02
1)
HMV
HMS
HMD
2)
PE
24V
1) third-party component (e.g. PLC, valve etc.)
2) connection to central ground point (e.g. earth-circuit connector)
Fig. 6-34: Installing the 24V supply
Note: If you use several power supply units for 24 V supply, make
sure that
• the reference conductors 0V of the individual power supply
units are interconnected with low impedance
• the output voltages of the power supply units are within the
allowed voltage range
• the power supply units are synchronously switched on and off.