Badly grounded control cabinet doors act as antennas. It is recommended
to connect the doors to the control section on top, in the middle and on
the bottom via short equipment grounding conductors with a cross section
of at least 6 mm
2
or, even better, via grounding straps with the same
cross section. Make sure connection points have good contact.
Fig. 6-31: Separation of interference-free area and interference-susceptible
area in control cabinet