Specifications
29
TROUBLE SHOOTING - SYMPTOM, CAUSE AND ACTION
(Continued)
SYMPTOM CAUSE ACTION
No LCD display *The LCD has been dimmed. *Touch LCD screen.
*Voltage to the humidifier is not that which is *Change humidifier or make necessary changes to
required per rating label. confirm compatibility.
*3 phase voltage but not all legs have power. *Check electrical connections and make necessary
repairs or hook ups.
*Internal or external circuit breakers are not *Close all circuit breakers.
closed.
*24 VAC supply to circuit board is not available. *Make sure the protection on the transformer is not
tripped (fuse or breaker). Confirm the required 24
VAC is leaving transformer. Make sure connection
to circuit board at J1 is intact. If situation does not
resolve, replace circuit board.
Humidifier unable to *Capacity of unit is too low. *Determine proper load calculation & capacity of
reach maximum output humidifier. Use properly sized unit.
or required set-point *Too high of a system static pressure. *Supply air system must be evaluated if static
pressure is too high. Located & correct issue.
*Back pressure in steam hose too high. *Too long of steam line runs, sags, dips, horizontal
runs not allowing for proper condensate removal,
improper sloping of steam lines & condensate line.
*Foaming. *Remove impurities inside the cylinder. If cleaning
of cylinder was attempted, throw away.
*Wrong cylinder. *Make sure proper cylinder and configuration is
used.
WATER CONTROL
The water contained in the cylinder must be controlled, in order for the humidifier to function properly. The fill and drain
rates must be maintained. Filling too quickly can cause over-amping and automatic shutdown, circuit breaker tripping or
blown fuses. Filling too slowly can cause insufficient steam output or insufficient humidity levels. Water supply pressure
should be between 30 and 80 psig, ideally 55 to 60 psig. Draining too quickly can cause dangerous arcing and elec-
trode corrosion. Draining too slowly can cause over-concentration and malfunction due to foaming. These are just some
examples of what can go wrong if the fill and drain rates are not controlled and maintained.










