Specifications
28
TROUBLE SHOOTING - SYMPTOM, CAUSE AND ACTION -
Table 6
SYMPTOM CAUSE ACTION
Arcing *Naturally very high conductivity water. *Water may be too high in conductivity. Test water.
*Drain lines restricted causing low water levels. *Inspect & clean drain & tubing regularly.
*Defective drain solenoid valve. *Repair, clean or replace as necessary.
*Insufficient flow of incoming water. Levels low. *Maintain 20 psi or above. Clean strainer, repair,
clean or replace fill solenoid as necessary.
*High back pressure in steam line. *Check kinks or severe bends in steam hose.
Check system static pressure.
*Excessive lengths of steam hose and/or *Shorten distance between humidifier & dispersion,
high static pressure. maintain proper incline in steam hose, eliminate as
many 90° or 45° bends, insulate steam line as
necessary.
*Attempted cleaning of cylinder by flushing or *Do not use solutions to clean cylinders, dispose
banging producing flakes causing restricted as necessary. Solutions could cause chemical
lines. reactions not conducive to good operation.
“Service” indicator on *Various. *See “Service Required” page for more information
regarding the problem.
Water doesn’t fill *All 4 basic control signals not satisfied. *Make sure all control circuits are closed and the
into cylinder (gray fill humidifier is ‘On’.
valve indicator)
Water doesn’t fill *Fill valve strainer is restricted. *Remove strainer from fill valve assembly and
into cyclinder (green fill) clean.
valve indicator) * Fill valve is defective. *Repair or replace as necessary.
*24 Volts AC not coming from circuit board. *Consult factory, replace circuit board.
Humidifier drains *Piece of mineral is partially blocking drain so *Cycle drain. If it does not clear, clean as
continuously it will not close properly. necessary.
*Drain plunger is worn out, preventing drain *Repair or replace as necessary.
valve from closing completely.
Water in duct or spitting *Steam hose & condensate return hose do not *Improve routing of all hoses and/or install
from distributor pipe have a continuous slope. Condensate condensate drains as necessary. Add a trap in the
accumulates and gets pushed out distributor. steam hose in front of the distributor.
*Condensate return is blocked, kinked and *Eliminate restriction in hose and routes as
prevents proper drainage of condensate required for proper flow of condensate water.
water and accumulates in distributor pipe
and pushed out into duct.
*Distributor pipe not installed properly or *Re-assemble, repair or replace as necessary.
manufactured properly, not allowing for a
continuous backward slope to steam hose and
condensate hose connection.
*If condensate return hose has a drop less then *Route the condensate return to a common drain
12”. and include a trap.
*Condensate return is connected to top of unit, *Whenever condensate hose is returned to top of
but a trap was installed too close to elbow, unit a trap is not required, remove it. Distributor
split, turning vane, grille or diffuser. pipe must be a minimum of 6 ft. upstream from
elbows, grilles, etc. If temp. in duct is 60°F or lower
the distance should be 10 ft. If distance, as
mentioned, is not possible, a drain pan may be
required. If the air in the duct can not hold the
volume of steam, the only recourse is to reduce the
maximum output of the unit. If very short
absorption distances are required, a short
absorption manifold can be installed.










