Specifications
26
CARNES STEAM MANIFOLDS reduce the non-wetting distance when
required because of space constraints in duct system.
SHORT ABSORPTION
MANIFOLD
Carnes Steam Manifolds are designed to pro-
vide dry steam with rapid absorption in the duct
air stream. It achieves this by distributing steam
evenly across the face of the duct. The distance
needed for absorption is dependent on a number
of factors, some of which are air velocity, steam
volume, air temperature and characteristics of
air flow in the duct. For minimum absorption
distance, the manifold should be located in the
warmest air stream of the duct and where fully
developed laminar air flow occurs.
• 304 Stainless steel steam distribution
tubes on three inch centers provide
extremely short absorption distances
• 304 Stainless steel manifold with
flexible EPDM connections for thermal
expansion without use of “O” rings
• Strong galvanized flanged frame for
easy and fast connection to duct
• Factory assembled for reduced
installation costs.
DESIGN
SERIES
TYPE WIDTH HEIGHT
H X M A C
0
3 6 0 2 4
018 = 18”
Through
072 = 72”
(2” Increments)
012 = 12”
Through
048 = 48”
(2” Increments)
B = “AX” or “B” Cylinder
C = 1 “C” Cylinder
D = 2 “C” Cylinders
Table 5
Duct Height Tubes
012
3
014
016 4
018
5
020
022 6
024
7
026
028 8
030
9
032
034 10
036
11
038
040 12
042
13
044
046 14
048 15
1-1/2”
(38)
1-1/2”
(38)
Duct Width
4”
(102)
3” (76)
3” (76)
Duct
Height
3-1/2” (89)
5”
(127)
6”
(152)
Type
B, C
Type
D