Specifications
23
FAN DISTRIBUTION UNITS
Fan distribution units are available for use in areas which do not
have duct systems or where duct air temperatures are too low
to provide sufficient humidification. For example, in computer
areas, the desired relative humidity may not be possible in the
conditioned space without causing condensation in the duct.
Fan distribution units may be either remote mounted or directly
mounted on the humidifier unit.
Humidifier
Model
Nominal Steam
Output Rate
Remote Mounted
Fan Unit Model
H_AH 005, 010 HXBHB (1 Required)
H_DH 020, 030 HXBHB (1 Required)
H_GH 030, 040, 050, 060, 080, 100 HXBHC (1 Required)
H_HH 125, 150, 175, 200 HXBHC (2 Required)
A Mounted Fan Distribution Unit and its associated humidifier
are shipped as a complete assembled unit. In this case, a 12-wire
connection is made from the circuit board to the 12-Pin fan
connection (Green). This connection is already assembled in the
factory.
Photo J
Fans
Steam
Hose
Fan distribution units must be mounted securely on a level and
plumb surface at least three feet below the ceiling for a Model
HXBHB and at least four feet below the ceiling for a Model HXBHC
to prevent condensing on the ceiling surface. Allow 20 feet in front
of the HXBHB and 30 feet in front of the HXBHC for the steam to
be absorbed into the air. Do not mount the units above any items
that would be damaged if a water leak or spitting were to develop.
Photo K
Fans
12-Pin Fan
Connection
Fans
Box
Photo L
Cooling
Fan
Inlet
Cooling Fan included with all fan distribution units as well as with
all other units manufactured (exception is residential). As soon as
power is suppled, the fan will start to run from the 12 volt service
from circuit board.
Cooling fan for
circuit board
when mounted
and remote fan
distribution unit
is used.
999-5739
31-3/8”
25”
20”
6-3/8”
11-3/4”
6-3/8”
9-5/8”
12-1/2”
12-1/2”