Specifications

11
ELECTRICAL DATA AND UNIT DETAIL SHEET - Table 4 (continued)
Model
Max
Lb/Hr Voltage Phase kW
Line
Amp
Disc.
Size
Optional
Circuit
Breaker*
Steam
Cylinder
Cyl Wire
Current
HBGH
HCGH
HSGH
HTGH
H_GHCU 50 208 3 17.2 47.8 80 2-35 Amp C62 23.9
H_GHEU 50 230 3 17.2 43.2 70 1-60 Amp C62 21.6
H_GHTU 50 380 3 17.2 26.2 40 1-40 Amp C65 26.2
H_GHWU 50 415 3 17.2 24.0 40 1-40 Amp C65 24
H_GHGU 50 460 3 17.2 21.6 35 1-30 Amp C65 21.6
H_GHHU 50 575 3 17.2 17.3 30 1-25 Amp C65 17.3
H_GHCU
* 60 208 3 20.7 57.4* 90 2-40 Amp* C62 28.7
H_GHEU
* 60 230 3 20.7 51.9* 80 2-40 Amp* C62 26
H_GHTU 60 380 3 20.7 31.4 50 1-50 Amp C65 31.4
H_GHWU 60 415 3 20.7 28.8 45 1-45 Amp C65 28.8
H_GHGU 60 460 3 20.7 26.0 40 1-40 Amp C65 26
H_GHHU 60 575 3 20.7 20.8 35 1-30 Amp C65 20.8
H_GHCU
* 80 208 3 27.5 76.5* 125 2-60 Amp* C62 38.2
H_GHEU
* 80 230 3 27.5 69.2* 110 2-50 Amp* C62 34.6
H_GHTU 80 380 3 27.5 41.9 70 1-60 Amp C12 21
H_GHWU 80 415 3 27.5 38.4 60 1-60 Amp C12 19.2
H_GHGU 80 460 3 27.5 34.6 60 1-50 Amp C12 17.3
H_GHHU 80 575 3 27.5 27.7 45 1-40 Amp C12 13.9
H_GHCU
* 100 208 3 34.4 95.6* 150 2-60 Amp* C62 47.8
H_GHEU
* 100 230 3 34.4 86.4* 150 2-60 Amp* C62 43.2
H_GHTU
* 100 380 3 34.4 52.3* 110 2-50 Amp* C12 34.2
H_GHWU 100 415 3 34.4 47.9 80 2-40 Amp C12 24
H_GHGU 100 460 3 34.4 43.3 70 1-60 Amp C12 21.7
H_GHHU 100 575 3 34.4 34.6 60 1-50 Amp C12 17.3
HBHH
HCHH
HSHH
HTHH
H_HHCU
* 125 208 3 43 119.5* 200 4-40 Amp* C62 (2) 29.8
H_HHEU
* 125 230 3 43 108* 175 4-40 Amp* C62 (2) 27
H_HHTU
* 125 380 3 43 65.3* 100 2-50 Amp* C12 (2) 16.3
H_HHWU
* 125 415 3 43 59.8* 90 2-45 Amp* C12 (2) 15
H_HHGU
* 125 460 3 43 54.0* 90 2-40 Amp* C12 (2) 13.5
H_HHHU 125 575 3 43 43.2 70 2-30 Amp C12 (2) 10.8
H_HHCU
* 150 208 3 51.7 143.5* 225 4-50 Amp* C62 (2) 35.8
H_HHEU
* 150 230 3 51.7 129.7* 200 4-50 Amp* C62 (2) 32.4
H_HHTU
* 150 380 3 51.7 78.6* 125 2-60 Amp* C12 (2) 19.7
H_HHWU
* 150 415 3 51.7 71.9* 110 2-60 Amp* C12 (2) 18
H_HHGU
* 150 460 3 51.7 64.8* 100 2-50 Amp* C12 (2) 16.2
H_HHHU
* 150 575 3 51.7 51.9* 80 2-35 Amp* C12 (2) 13
H_HHCU
* 175 208 3 60.3 167.3* 300 4-60 Amp* C62 (2) 41.8
H_HHEU
* 175 230 3 60.3 151.3* 250 4-60 Amp* C62 (2) 37.8
H_HHTU
* 175 380 3 60.3 91.6* 150 4-35 Amp* C12 (2) 22.9
H_HHWU
* 175 415 3 60.3 83.9* 150 2-60 Amp* C12 (2) 21
H_HHGU
* 175 460 3 60.3 75.6* 125 2-60 Amp* C12 (2) 18.9
H_HHHU
* 175 575 3 60.3 60.5* 100 2-50 Amp* C12 (2) 15.1
H_HHCU
* 200 208 3 68.9 191.2* 300 4-60 Amp* C62 (2) 47.8
H_HHEU
* 200 230 3 68.9 172.9* 300 4-60 Amp* C62 (2) 43.2
H_HHTU
* 200 380 3 68.9 104.7* 175 4-40 Amp* C12 (2) 26.2
H_HHWU
* 200 415 3 68.9 95.9* 150 4-35 Amp* C12 (2) 23.9
H_HHGU
* 200 460 3 68.9 86.4* 150 2-60 Amp* C12 (2) 21.6
H_HHHU
* 200 575 3 68.9 69.2* 110 2-50 Amp* C12 (2) 17.2
* = Circuit Breaker is REQUIRED per NEC 48 amp guideline.