Humidifiers Humidifiers | Steam Humidifiers COMMERCIAL, INDUSTRIAL AND INSTITUTIONAL STEAM HUMIDIFIERS HCHH Shown www.carnes.
Humidifiers | Steam Humidifiers Humidifiers CARNES MICROPROCESSOR CONTROLLED STEAM HUMIDIFIERS use ordinary untreated tap water and convert it to mineral free steam for humidity control in commercial, industrial, institutional and residential applications.
FRONT PANEL DISPLAYS & CONTROLS The display on the front panel of the humidifier cabinet contains the “On-Off-Drain” switch, the LCD True Touchscreen display and the “Fill”, “Drain” and “High Water” LED’s. “DRAIN” LED The DRAIN LED is a red light illuminated when the Drain Valve is activated. An activated Drain Valve allows water to drain from the humidifier. An analogous indicator, and a description of its operation, is offered in the “Component Activity” menu.
Humidifiers | Displays & Internal Controls Humidifiers Required” page for more information. 5. Maize — 8. Steam (orange) - Explains the status of the “Steam” indicator light. The humidifier will only produce steam if the “Steam” indicator light is green. The indicator will be brown when the On/Off/Drain switch is in the “Off” position.
The Control humidistat, which provides the Control Demand, is normally the humidistat in the room being humidified. It is either installed in the room itself or the return air duct. The High-Limit humidistat, which provides the Hi-Limit Demand, is a safe-guard humidistat installed in the supply duct roughly 10-15 feet past the distribution tube. This humidistat is usually set to a high level (8090%), and will shut down the humidifier if the humidity gets too high in the supply duct.
Humidifiers | Displays & Internal Controls Humidifiers “SETTINGS” of the humidifier. The Maximum Output value, when changed, also changes the Max Setpoint value on the Setpoints page. Cylinder Life Counter – The Settings menu is the page where all operational values can be set. It is password protected by default, with a default password of ‘1212’. The password can be disabled under the ‘Settings Password’ on the second Settings page. See ‘Settings Password’ section for more details.
Humidifiers Humidifiers | Displays & Internal Controls Setpoint Timeout – Boil Down Timer – This page is where the Setpoint Timeout value is set. The maximum amount of time allowed for the unit to reach setpoint during a fill sequence is designated by the Setpoint Timeout. Its default value is 30 minutes, but can be set as high as 255 minutes.
Humidifiers | Displays & Internal Controls Humidifiers Calibration Password – The help pages consist of maize color buttons labeled with questions. When a button is pressed, information will be given answering and/or giving information about the subject in question. A basic help page consists of text and/or diagrams to help the user through basic problems. This page is where the Humidifier Unit Code, the four digit number identifying the humidifier, is programmed into the unit.
APPLICATIONS OPERATION COMFORT Upon a signal from external controls the circuit board opens a fill solenoid valve, allowing water to flow across an air gap into a standpipe. The standpipe provides a column of water to be fed into the cylinder using gravity. The air gap prevents back flow into the water supply and prevents the cylinder from becoming a pressure vessel. The steam cylinder operates at a pressure of approximately 1/2 psi.
Humidifiers | System Design Consideration Humidifiers LOCATING THE HUMIDIFIER Locate the humidifier cabinet level and plumb on a surface as close to the steam distributor as possible at a convenient height for servicing. Allow 1” or more on the sides for ventilation and 16” from the bottom of the unit to the floor to allow for drain connections. Allow 14” in front of cabinet for door opening (Figure B).
STEAM DISTRIBUTOR PIPE LOCATION (Continued) Steam distributor pipes must be located on a plumb surface so condensate that forms will run back into the return line. The pipe should be located in the center of the duct to insure even distribution of steam into the airstream. A minimum clearance of 4” must be maintained between the top of the duct and the distributor pipe. The steam distributor pipes are usually located in the supply duct downstream of the fan.
Humidifiers | Controls Humidifiers CONTROL OPTIONS - Figure G CONTROL HUMIDISTAT AIR FLOW DETECTION CONDENSATION PROTECTION WALL HUMIDISTAT PROPORTIONAL CONTROL CARNES MODEL HXHCG OR WALL HUMIDISTAT (NEW) PROPORTIONAL CONTROL CARNES MODEL HXHAM OR WALL HUMIDISTAT ON-OFF CONTROL CARNES MODEL HXHAA OR DUCT HUMIDISTAT PROPORTIONAL CONTROL CARNES MODEL HXHCH OR DUCT HUMIDISTAT (NEW) PROPORTIONAL CONTROL CARNES MODEL HXHAN PRESSURE DIFFERENTIAL SWITCH CARNES MODEL HXAAE OR AIR FLOW SWITCH CARNES MODEL HXAAF
CONDENSATION PROTECTION A third device may be desirable to provide condensation protection in the duct system. A high limit humidistat may be installed ten (10) feet downstream from the steam distributor pipe. This humidistat is normally set to 90-95% RH and opens the circuit if the humidity level in the duct exceeds the set-point.
Humidifiers | Unit Availability Humidifiers MODELS AVAILABLE AND ELECTRICAL DATA - Table 8 HBAH HCAH HSAH HTAH HBDH HCDH HSDH HTDH HBGH HCGH HSGH HTGH Model H_AHAU H_AHBU H_AHDU H_AHFU H_AHLU H_AHQU H_AHMU H_AHNU H_AHAU H_AHBU H_AHDU H_AHFU H_AHLU H_AHQU H_AHMU H_AHNU H_DHBU H_DHDU H_DHFU H_DHLU H_DHQU H_DHMU H_DHNU H_DHCU H_DHEU H_DHTU H_DHWU H_DHGU H_DHHU H_DHCU H_DHEU H_DHTU H_DHWU H_DHGU H_DHHU H_GHBU* H_GHDU H_GHFU H_GHLU H_GHQU H_GHMU H_GHNU H_GHCU H_GHEU H_GHTU H_GHWU H_GHGU H_GHHU Max Lb/Hr 5
MODELS AVAILABLE AND ELECTRICAL DATA - Table 8 HBGH HCGH HSGH HTGH HBHH HCHH HSHH HTHH Model H_GHCU H_GHEU H_GHTU H_GHWU H_GHGU H_GHHU H_GHCU* H_GHEU* H_GHTU H_GHWU H_GHGU H_GHHU H_GHCU* H_GHEU* H_GHTU H_GHWU H_GHGU H_GHHU H_GHCU* H_GHEU* H_GHTU* H_GHWU H_GHGU H_GHHU H_HHCU* H_HHEU* H_HHTU* H_HHWU* H_HHGU* H_HHHU H_HHCU* H_HHEU* H_HHTU* H_HHWU* H_HHGU* H_HHHU* H_HHCU* H_HHEU* H_HHTU* H_HHWU* H_HHGU* H_HHHU* H_HHCU* H_HHEU* H_HHTU* H_HHWU* H_HHGU* H_HHHU* Max Lb/Hr 50 50 50 50 50 50 60 60 60 60 60 60 80
Humidifiers | Unit Availability Humidifiers NOTES: Identifying and explaining the electrical data and unit detail in Table 8 on the previous page “Model” and “Optional Circuit Breaker” columns designate presence, quantity and amp rating of optional circuit breakers. In addition, as an option, internally mounted, switchable on-off, circuit breakers are available in models preceded by “HB” or “HT”. PLEASE NOTE: Certain units require circuit breakers per NEC 48 amp guidelines. “Maximum Lb./Hr.
1 Model 2 3 Design Series 4 H B A H Electrical 5 6 A U Nominal Steam Output Capacity 7 8 9 0 1 Humidifiers Humidifiers | Unit Nomenclature Options 10 0 H - Humidifier B - With Internal Circuit Breakers* C - Without Internal Circuit Breakers S - Stainless Steel (304) Cabinet (w/o Breakers) T - Stainless Steel (304) Cabinet (w/ Breakers) UNIT TYPE A - 1 “AX” Cylinder D - 1 “B” Cylinder G - 1 “C” Cylinder H - 2 “C” Cylinders VOLTAGE A - 115V, 1PH B - 208V, 1PH C - 208 V, 3PH D - 230V, 1PH E
Humidifiers | Accessories Humidifiers STEAM DISTRIBUTOR PIPES Lengths 012-036 5” (127) 9-1/2” (241) T 3/8” N Lengths 048-120 4” (102) T 4” (102) N 3/8” Distributor Pipes for Models: H_AH, H_DH PIPE N T HXPBB012S 11-13/16 (300mm) 7/8 PIPE N T HXPBB018S 17-13/16 (452mm) 7/8 HXPBC012S 11-13/16 (300mm) 1-5/8 HXPBB024S 23-13/16 (605mm) 7/8 HXPBC018S 17-13/16 (452mm) 1-5/8 HXPBB030S 29-13/16 (757mm) 7/8 HXPBC024S 23-13/16 (605mm) 1-5/8 HXPBB036S 35-13/16 (910mm) 7/8 HXPBC03
FAN DISTRIBUTION UNITS OPTIONS STANDARD MOUNTING: Factory attached to humidifier. OPTION: Mounted remote from humidifier.
Humidifiers | Accessories Humidifiers WALL HUMIDISTAT, PROPORTIONAL CONTROL DUCT HUMIDISTAT, PROPORTIONAL CONTROL Model HXHAM Model HXHAN The Model HXHAM is a wall-mounted, microprocessorcontrolled humidistat solution for cutting edge humidity control. The HXHAM employs a backlit LCD module, which displays both the ambient temperature and humidity of the surrounding air.
DUCT HUMIDISTAT, ON-OFF CONTROL Model HXHAB This duct mounted humidistat mounts in the return air duct to provide control of the humidifier. The control should be located in the duct where it will be affected by normal air flow. The maximum temperature at the nylon element must not exceed 125°F. The control can be mounted in any position, but where possible locate it on the side of the duct to make the set-point adjustment easily accessible. Scale range is 15%-50% RH Differential is 4%-6% non-adjustable.
Humidifiers | Accessories Humidifiers AIR FLOW SWITCH PRESSURE DIFFERENTIAL TYPE Model HXAAE Air flow in the duct may be sensed by using this differential pressure switch. The differential in pressure between the interior of the duct and ambient when air is moving in the duct closes a micro switch allowing the humidifier to operate. Air pressure differential as low as .07 w.g. and as high as 12.0 w.g. may be sensed with one model. The switch may be mounted with tubing connecting to the duct.
Humidifiers Humidifiers | Accessories STEAM HOSE CONDENSATE RETURN LINE Carnes steam hose is made from EPDM compound to withstand the low pressure steam without deterioration. Model HXSAB steam hose has an I. D. of 7/8” for use with units that use “AX” or “B” steam cylinders. Model HXSAC has an I. D. of 1-5/8” for use with units that use “C” cylinders. The hose may be easily cut to the exact length at time of installation. Two models of condensate return line are available. Model HXRA has an I. D.
Humidifiers | Accessories Humidifiers DRAIN WATER PUMP Inlet Grommet For 7/8” O. D. Hose Micro Switch Controlled By Float 3-Prong Molded Cap 9” Overflow 3000 R. P. M. 1.4 AMP Open Motor 3-1/4” 2 Gallon Reservoir Of Cast Aluminum Epoxy Clad Access Cover Plate 4-5/8” x 5” Model HXWA A drain water pump is available for mounting directly below the humidifier cabinet.
Humidifiers | Humidifier Dimensions Humidifiers MODELS: H_AH H_DH H_GH Condensate Return Inlet Steam Output 8.375 (213) 5.125 (130) TOP 10.625 (270) 9.000 4.654 (229) (118) 5.875 (149) 7.590 (193) 19.968 (507) Mounting Flange 24.947 (634) 11.703 (297) SIDE 19.813 (503) 5.613 (143) Drain Pipe 4.750 (121) NOTE: Drain Pipe is NOT an air gap fitting. BOTTOM 1-1/2” PVC Air Gap Connection 1.505 (38) 1-3/8” Dia. Hole For Power Wiring 3/8” FPT Water Inlet 3.069 (78) 1.500 (38) 1.
Humidifiers | Humidifier Dimensions Humidifiers MODELS: H_HH 31-3/4” (806) Condensate Return Inlet TOP 19-5/8” (498) 6” (152) Condensate Return Inlet 12-1/2” (318) Mounting Flange Steam Outlets 38” (965) 20-1/4” (514) 26” (660) 5-5/8” (143) NOTE: Drain Pipe is NOT an air gap fitting. 14-3/4” (375) Drain Pipe 25-3/4” (654) SIDE An air gap fitting must be included in drain plumbing set-up (non-Carnes installation). See picture If you wish to purchase an air gap from Carnes it is an option.
1. Provide self-contained microprocessor controlled steam generating humidifiers of the size(s) shown on plans as manufactured by Carnes Company, Verona, WI. 2. Carnes Humidifiers shall have the capacity to operate at 115, 208, 230, 277, 380, 415, 460 and 575 volt (or nominal value), 60 or 50 hz (cycle), single or 3 phase power. Specific combination of maximum output, voltage and phase for order application determined by electrical data chart. 3. The humidifier(s) shall be UL and cUL listed. 4.
Humidifiers | Residential Steam Humidifiers Humidifiers LIGHT COMMERCIAL & PREMIER HOME OR CONDOMINIUM STEAM HUMIDIFIERS Status display visible with door closed and locked. Hinged door provides full access for service. Steam cylinder easily removed for replacement. Two Sizes Available Size 005 satisfies areas up through 1400 square feet. Size 010 will humidify areas up through 2800 square feet under normal conditions. If multiple furnaces are used a separate humidifier should be used for each.
CARNES STEAM HUMIDIFIERS use a microprocessor, digital display and LED’s to provide superior operating and diagnostic functions to simplify troubleshooting and reduce maintenance costs. OPERATION Upon a signal from a humidistat the circuit board opens a fill solenoid valve, allowing water to flow across a 1” air gap into a standpipe. The air gap prevents back flow to the water supply and prevents the cylinder from becoming a pressure vessel.
Humidifiers | Residential Steam Humidifiers Humidifiers CARNES STEAM HUMIDIFIERS are designed for quiet, efficient operation and are easy to install. TYPICAL INSTALLATION Steam Distributor Pipe Air Duct Steam Hose Water Shutoff Valve Condensate Return Line Humidifier Cabinet Cold Water Line Fused Disconnect or Circuit Breaker Drain Line DISTRIBUTOR PIPE & HOSE DIMENSIONS HUMIDIFIER DIMENSIONS 7/8” Dia. Hole For Power Wiring 1/4” FPT Water Inlet 7/8” Dia.
CARNES STEAM HUMIDIFIERS are available with a complete selection of accessories to provide accurate humidity control. WALL HUMIDISTAT, PROPORTIONAL CONTROL Model HXHAM DUCT HUMIDISSTAT, PSROPORTIONAL CONTROL Model HXHAN The Model HXHAM is a wall-mounted, microprocessorcontrolled humidistat solution for cutting edge humidity control. The HXHAM employs a backlit LCD module, which displays both the ambient temperature and humidity of the surrounding air.
Humidifiers | Residential Humidifier Accessories Humidifiers AIR FLOW SWITCH, PRESSURE DIFFERENTIAL TYPE HIGH LIMIT HUMIDISTAT Model HXHAD Model HXAAE Air flow in the duct may be sensed by using this pressure differential switch. The differential in pressure between the interior and exterior of the duct closes a switch when air is moving. Air pressure differential as low as .07 w.g. may be sensed with this switch. Mounting plate dimensions are 4-3/4” wide, 5-1/8 high.
Humidifiers Humidifiers | Steam Manifold SHORT ABSORPTION MANIFOLDS FOR STEAM HUMIDIFIERS Carnes Steam Manifolds are designed to provide dry steam with rapid absorption in the duct air stream. It achieves this by distributing steam evenly across the face of the duct. The distance needed for absorption is dependent on a number of factors, some of which are air velocity, steam volume, air temperature and characteristics of air flow in the duct.
Humidifiers | Steam Manifolds Humidifiers CARNES STEAM MANIFOLDS are available in standard sizes from 18” x 12” through 72” x 48” in two inch increments. Additional special sizes are available. Table 3 Table 1 Air Pressure Loss, “w.g.” 500 fpm .02 750 fpm .
CARNES STEAM MANIFOLDS with strong galvanized flanged frames are factory assembled to reduce installation costs. LOCATION OF MANIFOLD The manifold is usually located in the supply duct downstream of the fan, heating coil, cooling coil and/or filter. When installed in packaged units, the manifold is to be mounted just downstream of the fan discharge. Figure A The non-wetting dimension is the distance necessary to prevent condensation on any obstruction downstream from the manifold.