I am looking for a 4" fiberglass conduit product. Do you make such a product?
Carlon does not make a fiberglass conduit. We do sell 4" fiberglass Multi-Gard
with three or four pre-installed innerducts, but not on its own. Two companies
come to mind: United Fiberglass (USA) and FRE Composites Inc. (Canada).
I am working for the U. S. Government for the "Office of Overseas Buildings
Operations (OBO). We have procured big quantity of "Carlon plus 40 rigid non
metallic conduits" for the project work, being executed in Abu Dhabi. Please
advice us of your recommendation on storage of "Carlon plus 40 rigid non
metallic conduits". Can "Carlon plus 40 rigid non metallic conduits" be stored in
an open to sky area in direct sunlight, the temperature in this region goes up to
50C to 55C with 100% humidity.
Carlon Schedule 40 PVC Conduit is designed for outdoor applications in all
weather conditions. Therefore can be stored outside without any additional
protection. We recommend when stacking the crates that the wood "slates" used
to bundle the conduit are placed on top of each other and not directly onto the
conduit.
What is the difference between sch 40 and sch 80? What applications would you
use one compared to using the other one?
Schedule 80 Conduit will have a thicker wall. OD's will remain the same. Section
347-3(c) of the 1999 NEC (352.12(C) of the 2002 NEC) states that Rigid
Nonmetallic Conduit is not permitted where subject to physical damage unless
identified for such use.
Schedule 80 conduit is listed and identified for the areas of physical damage. If
you are concerned with impacts or crushing after the raceway has been installed
than schedule 80 conduit should be used.