Specifications

37
Compact Power Transducer CPT DIN
Basic and Advanced functions
CPT DIN is a compact transducer available as a Basic
version for measurement and data retransmission and as
an Advanced version with many kinds of outputs and PLC
type control functions suitable to be used also for critical
applications. This unit for 3-phase and single-phase
systems is recommended for the measurements of both
main electrical variables in electrical distribution systems
and on board of machines as working survey equipment.
Moreover it represents an excellent compromise among
price, value and features.
The most important benefits in the advanced version are:
Integrated and extended AC and DC power supply for
full application coverage.
Metering of both total and partial active and reactive
energies in order to survey both load parameters and
consumptions.
Hour counter function for machine maintenance planning.
RS485 communication port (with iFIX SCADA
compatibility) for data transmission to PC, or pulse or
analogue outputs to PLC. All of them for remote
monitoring and control of the variables.
Dupline bus compatibility for full Building automation
integration.
OR, AND, OR+AND control of up to 16 selected
variables to grant together with the asymmetry, phase
sequence and phase loss functions an extended load or
line control by means of 2 digital outputs.
Combination of RS485 port and 1 digital output
83.5 x 45 x 98.5 mm
N.A.
4 DGTs format
8+1 DGTs format
5+2 DGTs format
W-VA:±(1% F.S.+1DGT)
var:±(2% F.S. +1DGT)
V
LL: ±(1.5% F.S. +1DGT)
V
LN-A:±(0.5% F.S. +1DGT)
kWh: class 1
kvarh: class 2
200ppm/°C
1.5 times/s
Unbalanced: 2-3-phase; bal.: 1-3-ph
100/208VAC, 400/660VAC
1/5AAC
N.A.
Prog.: CT up to 300kA; VT up to 600kV
TRMS method
Sys: V
LN,An,W, var, VA,Wdmd,Wdmd max,VAdmd,Hz
Wh, varh, h. Single-phase: V
LL,VLN,A,
Admd,Admd max, W, var, VA, PF.
N.A.
2 (open collector or relay)
16 with OR/AND function (2 relays)
Up to 3 (20mA, 10V DC)
RS422/485, RS232 (Modbus)
Action: on variables and outputs
Diagnostic function on available
outputs with dual colour LED indication
18 to 60VAC/DC, 90 to 260VAC/DC
CE; cURus, CSA
IP20
Housing (H x W x D)
Variables on display
Instantaneous variables
Energy variables
Hours
Accuracy
Temperature drift
Refresh rate
System type
Voltage inputs (Un)
Current inputs (In)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
Hardware Functions
In-Out
Performances
The best to suit your needs!
Comm
3
16
OR
OR
AND
The histogram is related to the Advanced version.
CptASoft, CptBSoft:
programming and reading
tools, see page 42.