Specifications
Hardware Functions
In-Out
Performances
The best to suit your needs!
96x96x129 (WM5); 90x90x140 (PQT H)
Graphic, back lighted LCD (WM5 only)
WM5 96: YES; PQT H: NO
WM5 96: 4x4 DGTs; PQT H: 4 DGTs format
4x9 DGTs
V
LN
-A:±(0.2 RDG+1DGT)
Hz:±0.1% F.S. THD: ±1% F.S.
Class 0.5 (ANSI C12.20, EN62053-22)
Class 2 (ANSI C12.1, EN62053-23)
≤200ppm/°C
10 times/s
Bal.: 1-3 phase; Unbal.: 3-phase
Autoranging 120/208VAC, 400/690VAC
Autoranging In: 1/5AAC; Imax: 10AAC
Up to 12 for W
dmd
,VA
dmd
synchro. and others
Prog.: CT up to 60,000A; VT up to 600kV
TRMS method
Sys:V
LN
,V
LL
, An, W, var, VA, PF, Hz, Wh, varh,
Single-phase: V
LN
,V
LL
, A, W, var, VA, PF,
THD.All variables: min-max-dmd calcul.
THD and single H up to the 63rd H (V, A)
Up to 16 (open collector or relay)
Up to 16 (open collector or relay)
Up to 8 ( ±5mA, +20mA, +10V DC)
RS485/232 (Modbus), Ethernet 10/100 base T
Action: on variables and outputs
Real time clock with alarms, Min/Max, digital
input status, reset data stamping; dmd
integration time programming, energy time
period management (up to 12 tariffs).
18 to 60VAC/DC, 90 to 260VAC/DC
CE, cURus, CSA, Revenue Approval
WM5: IP65 NEMA4x NEMA12; PQT H: IP20
Housing (H x W x D) mm
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Refresh rate
System type
Voltage inputs (Un)
Current inputs (In)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
WM5 96 is a Smart Power Quality Analyzer, while PQT H is
its corresponding transducer version. Both of them are
powered with ARM technology which improves
significantly the signal processing and the communication
speed compared to any other standard analyzer. The
superior features of these new meters are the right answer
to those applications where performances and high
accuracy are a MUST. Both WM5 96 and PQT H are
modular and flexible so to be suitable to the most
demanding applications. They offer many advantages and
solutions that can be summarised in:
• Revenue grade and revenue approval to be used also for
billing purposes thanks to their 0.2 accuracy class and the
compliance to ANSI/IEEE C12.20-1998 and CAN3-C17-M84;
• Real powerful cost control: complex and complete tariff
management (12 tariffs by 24 time periods/day);
• Extended load or line control with asymmetry, phase
sequence and phase loss functions: on up to 16 selected
variables linkable to up to 16 independent or
OR/AND/OR+AND logic controlled alarms;
• Complete interfacing capability: up to 12 digital inputs, up
to 16 pulse outputs, up to 8 analogue outputs, RS232,
RS485, or optical communication.
Comm
Optical
Optical
A/V
Class 0.2
Modular Smart Power Quality Analyzer WM5 96
Modular Smart Power Quality Transducer PQT H
WM5 96 PQT H
12
16
8
16
kWh
kWh
EN62053-22
EN62053-22
kvarh
kvarh
EN62053-23
EN62053-23
t12
t12
63h
THD V/ATHD V/A
34
PQT H
E
t
h
e
r
n
et
c
a
p
a
b
i
l
it
y
By AR1061 module (Modbus over TCP/IP)
Measurement Canada
An Agency of Industry Canada
WM5 96: Revenue Approval n° AE-1507